Select grid standard (Figure 7.24)
7.5.1 Select Grid Standard
NOTE:
The "User-Def" function can be only used by the service engineer and changing
protection level must be allowed by the local grid company.
NOTE:
This is for service technicians only. The inverter is customized according to the
local standard before shipping, there should be no requirement to set the
standard.
7.5 Advanced Settings - Technicians Only
Select Advanced Settings from the Main Menu to access the following options:
NOTE:
This function is for authorised technicians only. Improper access and operation
may result in abnormal results and damage to the inverter.
Password this function is for authorised technicians only.
Password (refer to 7.4 section) required – restricted access – authorised
technicians only. Un-authorised access may void the warranty.
The default password is "0010".
Figure 7.23 Advanced settings
Advanced Set.
2015-02-23 19 35
Select Standard
Grid ON/OFF
Power Control
Clear Energy
Restore Settings
Calibrate
Reset Password
7. General Operation
7. General Operation
Press the UP/DOWN keys to select the standard (AS4777,VDE4105,UL-1741, G59/3,
CQC and “User-Def” function). Press the ENTER key to confirm the setting. Press the
ESC key to cancel changes and returns to previous menu.
Selecting the User-Def submenu will access to the following submenu (see Figure 7.25):
Figure 7.24 Select national standards
Figure 7.25 User-Def
Select Standard
2015-02-23 19 35
Select Standard
G59/3
ESC
UP
DOWN
ENT
YES=<ENT> NO=<ESC>
User-Def
2015-02-23 19 35
OV-G-V1 :
OV-G-V2 :
UN-G-V1 :
UN-G-V2 :
OV-G-F1 :
OV-G-F2 :
UN-G-F1 :
UN-G-F2 :
Startup-T :
254V
265V
190V
172V
51.0Hz
52.0Hz
48.0Hz
47.0Hz
060s
OV-G-V1-T :
OV-G-V2-T :
UN-G-V1-T :
UN-G-V2-T :
OV-G-F1-T :
OV-G-F2-T :
UN-G-F1-T :
UN-G-F2-T :
Restore-T :
1.0s
0.2s
1.0s
0.2s
1.0s
0.2s
1.0s
0.2s
060s
.38.
.39.
NOTE:
Remark: This is the phase voltage (L-N) setting, and the corresponding line
voltage (L-L) is 1.732 times the setting value.