10

To change the other parameters (Second Level) follow these steps: 

 

Step 1 

 and 

 

Press and hold SET and DOWN for 10 seconds. The display 
will show 

dSPL

 

Step 2 

 

Press SET to change the parameter 

Step 3 

 or 

 

Press UP or DOWN to change the options, time or temperature 
for the current parameter  

Step 4 

 

Press SET to accept the new value 

Step 5 

 

Press DOWN to go to the next parameter, then go back to Step 
2. After the last parameter is displayed (

ALHi

), the display will 

go back to the normal operating condition 

 

Note: to scroll down the parameters without changing them, press the DOWN button. 
 
List of Parameters 
Here is a list of the parameters that can be changed in the Second Level of programming, as well as 
their options and ranges.  
Note:  Master-Bilt’s Set point Temperature (

Set)

 is set at a recommended –10

°

F at the 

factory.  

 

 

Parameter Displa

Symbo

Description 

Range / Options 

Master-

Bilt’s 

Factory 

Setting 

Display Status 

dSPL 

Information shown 

on the display 
during operation 
conditions  

tdAy

 – time-of-day 

rSP

°

 – zone temperature  

CyCL 

– cycle between time and 

zone temperature 

Epr

°

 

– evaporator coil temperature 

 
rSP 

Clock Format 

CLHr 

Time Format(12 or 

24 hours mode) 

12Hr

 – AM/PM format 

24Hr

 – 24 hour format  

12Hr 

Temperature 
Format 

°

dSP 

Temperature 

degrees 

°

F

 – degrees Fahrenheit 

°

C

 – degrees Celsius 

°

Defrost Type 

dFtP 

Type of defrost used 

in the application 

ELEC

 – electric defrost / off cycle 

HgAS

 – hot gas defrost  

ELEC 

Fan Status 
During Defrost 

EFAN 

Enable or not the 

fan during defrost 

no

 – fan is turned off during defrost 

yES

 – fan remains on during defrost  

No 

– for LT 

yES

–for MT

 

Fan Status 
During Normal 
Mode

 

CFAN 

Enable or not fan during 
normal compressor 

on/off mode

 

on 

– fan on during normal mode

 

CyCP 

– fan cycles with compressor

 

on 

Defrost 
Interval  

dFin 

Type of defrost 

interval 

TdAy

 – time-of-day setpoint 

CPrn

 – compressor run time 

tdEF 

– temperature initiated defrost 

ddEF 

– demand initiated defrost 

ddEF

–for LT

 

CPrn

–for MT

 

 
 

Minimum 
Compressor 
Off Time 

CoFF 

Minimum time that 

the compressor  
remain turned off  

Range: from 0 to 15 min  

2 min. 

Summary of Contents for TAF-27 ERC2 s

Page 1: ...Installation Operations Manual Master Bilt Products 908 Highway 15 North New Albany MS 38652 Phone 800 684 8988 PN 228 90000 Rev 05 04 04 bhs...

Page 2: ...2...

Page 3: ...TRUCTIONS 6 Inspection for ShippingDamage 6 INSTALLATION INSTRUCTIONS 6 General Instructions 6 Electrical 6 Leg and Condensate Pan Installation 7 ELECTRONIC REFRIGERATION CONTROL ERC 8 FINAL CHECK LIS...

Page 4: ...If this case is to be located against a wall there should be at least 6 space between the wall and the back of the case see page 7 This space will allow for the circulation of air behind the case whi...

Page 5: ...ing signal words are used in the warnings and safety messages DANGER Severe injury or death will occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUT...

Page 6: ...if the cabinet is malfunctioning or if there is a drainpipe leaking MECHANICAL Remove front grille and check refrigeration lines to see that they are free not touching each other or compressor Spin co...

Page 7: ...temperatures for short periods of time 6 When replacing burned out fluorescent tubes be sure that the electrical power to the lighting circuit is turned off ELECTRICAL WARNING Before servicing electr...

Page 8: ...s The TAF 27 models are cord connected and operate on a 15 amp 115 60 1 circuit The TAF 48 and TAF 74 models have two junction boxes mounted on top of the cabinet at the right rear for permanent conne...

Page 9: ...T to accept the new time Step 5 Press DOWN to go to the next parameter Set point Temperature cut out Step 6 Press SET to change the set point temperature Step 7 or Press UP or DOWN to go to the desire...

Page 10: ...Status dSPL Information shown on the display during operation conditions tdAy time of day rSP zone temperature CyCL cycle between time and zone temperature Epr evaporator coil temperature rSP Clock Fo...

Page 11: ...e Range from 0 to 15 min 2 for LT 0 for MT Pump Down Pudn Pump down duration Range from 0 to 59 min 0 min Drip Time driP Drip time duration Range from 0 to 59 min 2 for LT 0 for MT Setpoint Differenti...

Page 12: ...on the display Press SET to accept the change Press DOWN to go to Defrost Start Time dEF1 Press SET to change the time Press UP or DOWN until the 11 59 PM appears on the display Press SET Press DOWN...

Page 13: ...s in the probe the control has LED functions as a diagnostic tool When power is supplied to the control the LED will turn on and will remain on as long as this condition is satisfied When there is a f...

Page 14: ...Compressor starts and runs but cycles on overload A Low voltage B Dropped phase 3 phase C Overload protector defective D High head pressure see 1 6 Compressor will not start hums but cycles on overloa...

Page 15: ...Gasket 37 01207 37 01211 37 01211 Door Handle 35 01488 35 01488 35 01488 Door Hinge Assembly A35 01501 A35 01501 A35 01501 Door Light Switch 35 01506 35 01506 35 01506 Door Opening Trim 29 01481 29 01...

Page 16: ...ster Bilt at 800 684 8988 The customer service department at Master Bilt should be contacted at the time of sale or disposal of your cabinet so records may be kept of its new location If you sell or g...

Page 17: ...17...

Page 18: ...18...