background image

4. Circuit Protection     

5. Dimensional Drawing     

The batteries are supplied with a LiFePO4 Battery Management System (BMS) that can monitor and optimized 
each single prismatic cell during charge & discharge, to protect the battery pack overcharge, over discharge, 
short circuit. Overall, the BMS helps to ensure safe and accurate running.

UE-12Li50

Test Item

Over-charge protection for each cell

Criterion

Content

3.80±0.03V

Over charge

Over-charge release for each cell

3.60±0.05V

Over-charge release method

Under the release voltage

Over-discharge protection for each cell

2.50±0.05V

Over discharge

Over-discharge release for each cell

3.00±0.05V

Over-discharge release method

Over the release voltage

Discharge over current protection 

150~200A

Over current

Protection delay time

50~200ms

Over current release method

Release after 30s

Over Temperature

Battery CHG/DSG over temperature

Protection @65±5°C

Release @60±5°C

Battery CHG lower temperature

Protection @-10±5°C

Release @0±5°C