5
4.
Installation
4-1. Precaution
This hybrid inverter is designed for indoor or outdoor use (IP65), please make sure the
installation site meets below conditions:
Not in direct sunlight
Not in areas where highly flammable materials are stored.
Not in potential explosive areas.
Not in the cool air directly.
Not near the television Antenna or antenna cable.
Not higher than altitude of about 2000 meters above sea level.
Not in environment of precipitation or humidity (>95%).
Please AVOID direct sunlight, rain exposure, snow laying up during installation and
operation.
4-2. Selecting Mounting Location
Please select a vertical wall with load-bearing capacity for installation, appropriate
for installation on concrete or other non-flammable surfaces.
The ambient temperature should be between -25~60
℃
to ensure optimal
operation.
Be sure to keep other objects and surfaces as shown in the diagram to guarantee
sufficient heat dissipation and have enough space for removing wires.
For proper air ventilation to dissipate heat, allow a clearance of approx. 50cm to
the side and approx. 50cm above and below the unit. And 100cm toward the front.
4.3. Mounting Unit
Installation to the wall should be implemented with the proper screws. After that, the
device should be bolted on securely.
The inverter only can be used in a CLOSED ELECTRICAL OPERATING AREA. Only service
person can enter into this area.
WARNING!! Remember that this inverter is heavy! Please be carefully when lifting out
from the package.
WARNING!! FIRE HAZARD.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE
ONLY.