60
inverters connected in parallel.
Regarding cable size of AC input and output, please also follow the same principle.
CAUTION!! Please install a breaker at the battery side. This will ensure the inverter can
be securely disconnected during maintenance and fully protected from overcurrent of
battery.
Recommended breaker specification of battery for each inverter:
Model
One unit*
LV 6KW
200A/60VDC
*If you want to use only one breaker at the battery side for the whole system, the rating
of the breaker should be X times current of one unit. “X” indicates the number of
inverters connected in parallel.
Recommended battery capacity
Inverter parallel
numbers
2
3
4
5
6
Battery Capacity
400AH
600AH
800AH
1000AH
1200AH
CAUTION! Please follow the battery charging current and voltage from battery spec to
choose the suitable battery. The wrong charging parameters will reduce the battery
lifecycle sharply.
Approximate back-up time table
Load (W)
Backup
Time
@ 48Vdc
400Ah
(min)
Backup
Time
@ 48Vdc
600Ah
(min)
Backup
Time
@ 48Vdc
800Ah
(min)
Backup
Time
@ 48Vdc
1000Ah
(min)
Backup
Time
@ 48Vdc
1200Ah
(min)
12000
90
140
180
240
280
18000
60
90
120
160
180
24000
40
70
90
120
140
30000
35
55
75
90
110
36000
30
50
60
80
100
PV Connection
Please refer to user manual of single unit for PV Connection.
CAUTION: Each inverter should connect to PV modules separately.