background image

 

insulating blocks to allow air to circulate beneath may be used. There must be at least a
12mm high gap unobstructed along at least two thirds of each side, and care must be
taken  to ensure that this amount of space will not be encroached on by laying carpet
etc. To be safe, a 25mm high gap is recommended. If preferred, instead of having a gap
under the concrete slab, it may be poured on top of two sheets of Micore 160 lying
directly on the floor. If cast in place, an impermeable sheet must be laid on top of the
Micore to prevent water damage from the concrete mix. Constructions which are NOT
suitable as insulating hearths are bricks and concrete when they are in contact with heat
sensitive flooring material.

In all cases, in both countries, a durable top surface will be needed to resist damage
from dropped embers. Obvious choices are slate, bricks and ceramic tiles. Gaps in the
top surfacing material must be grouted to prevent embers from penetrating. A trim
moulding will provide a neat edge finish.

Floor

Australia — Not less than 18mm thickness of  fibre cement board
New Zealand — Two sheets of MICORE160 or
one sheet of WOODTEX (35 thick)

Ceramic tiles

Trim moulding

Recommended hearth constructions are:-

FITTING A WATER COIL

Water heating coils can be fitted to Arcadia and Utopia heaters. The pipe attachment
positions are shown below.

B

Heater

A

B

Arcadia

Utopia

 280

310

590

 520

C

Alternate flue position at rear

C

495

550

All plumbing work must meet the requirements of local Building Codes. Pipe

connections are 1” BSP. Special piping methods must be followed to ensure effective
circulation, and the hot water cylinder will need to have an internal riser pipe to two
thirds of the cylinder height to discourage unwanted water circulation through the
piping system when the heater is not burning. This internal riser pipe must be connected
to the return pipe from the heater.

Piping instructions are included with the kit. Two safety requirements must be stressed.

THERE MUST BE NO NON-RETURN OR SHUT-OFF VALVES IN THE PIPES
BETWEEN THE HEATER AND THE STORAGE CYLINDER.

A HEATER FITTED WITH A WATER HEATING BOOSTER MUST NOT BE
FIRED UNLESS IT IS CONNECTED TO A VENTED STORAGE CYLINDER
FILLED WITH WATER FREE TO CIRCULATE.

8

Summary of Contents for ARCADIA

Page 1: ...ARCADIA UTOPIA UTOPIA Series 2 GRAND UTOPIA SOLID FUEL HEATERS INSTALLING AND OPERATING INSTRUCTIONS 585877 ...

Page 2: ...ou should approach your local Building Authority before commencing installation to establish whether you will require a Permit and whether you will need to meet extra requirements MASPORT radiant heaters have been tested to ensure that they will meet the appropriate safety Standard requirements if the instructions in this book are followed PLEASE ENSURE THAT ONLY COMPONENTS APPROVED BY MASPORT ARE...

Page 3: ...lign with the back edge of the top of the heater and the extension should fit snugly against the top casting Raise the heater into its upright position again taking care not to damage the floor Before fitting the firebox ceiling baffle first locate the four support lugs which will support it near the top of the firebox Insert the baffle into the firebox ensuring that the curved centre section is a...

Page 4: ...nts for a fireplace installation Finalise the installation position for your woodfire only after considering the necessary heater to wall distances see below and checking the practicability of installing the flue system through the ceiling and roof or wall As a guide the flue shielding and the 25mm clearance gap around it in the ceiling space will occupy a diameter of approximately 300mm and this ...

Page 5: ... 25 mm2 i e 15 000mm2 So if the effective length of each slot is 1m it will need to be 15mm wide Three types of shield are recommended Type Layers Spacing Clearance Factor A One 12mm 0 4 B One 25mm 0 3 C Two 12 12mm 0 2 Valid only for shields within 45 of vertical To find the reduced minimum distances multiply the figures in columns A B and E from the Table on page 4 by the appropriate clearance f...

Page 6: ...A G H J G l a ss W 360 min Wall Minimum dims for A are on page 4 See Notes below MINIMUM HEARTH EXTENSIONS mm WHEN THE REAR HEAT SHIELD IS FITTED Rear Heat Shield W B C D G H J Australia New Zealand New Zealand hearth flush hearth 50mm high Arcadia Utopia Arcadia Utopia Arcadia Utopia 855 635 300 165 150 335 525 1075 760 425 275 150 335 525 975 680 345 225 150 335 525 1165 980 550 275 155 430 615 ...

Page 7: ...X Y NOTE YOUR SPECIFIC MEASUREMENT FOR E MUST BE ADDED TO X AND Y TO FIND THE APPROPRIATE MINIMUM HEARTH DIMENSIONS SEE PAGE 4 FOR MINIMUM VALUES OF E MINIMUM DIMENSIONS Millimetres Australia 750 430 New Zealand hearth 50mm high New Zealand hearth flush Arcadia Utopia Utopia Utopia Arcadia Arcadia 800 540 750 470 1050 730 1000 680 850 550 HEARTH CONSTRUCTION In Australia the minimum hearth constru...

Page 8: ...Australia Not less than 18mm thickness of fibre cement board New Zealand Two sheets of MICORE160 or one sheet of WOODTEX 35 thick Ceramic tiles Trim moulding Recommended hearth constructions are FITTING A WATER COIL Water heating coils can be fitted to Arcadia and Utopia heaters The pipe attachment positions are shown below B Heater A B Arcadia Utopia 280 310 590 520 C Alternate flue position at r...

Page 9: ...apter 7 1985 except that the specified separation between the outside of the chimney and timber construction need not be complied with A flue pipe must be fitted right up the chimney and the space between the flue pipe and chimney must be ventilated at the top In Australia the area of this vent must be not less than 10 000mm2 while in New Zealand it is 13 000mm2 The vent must be fitted with means ...

Page 10: ...ing instructions will ensure satisfactory performance The use of wood with greater than 25 moisture is not permitted MAKE SURE THE MINIMUM HEATER TO WALL DISTANCES SHOWN ON PAGE 4 ARE ALWAYS MAINTAINED BETWEEN THE HEATER AND ANY HEAT SENSITIVE MATERIAL SUCH AS FURNITURE WINDOW DRAPES FUEL ETC DO NOT ATTEMPT TO BURN LIQUID FUELS OF ANY KIND LIGHTING UP Before lighting the first fire spread the sand...

Page 11: ...LED YOU MAY HAVE TO LEAVE A DOOR SLIGHTLY OPEN AND PERHAPS A WINDOW ELSEWHERE IN THE HOUSE IF YOUR HOME IS OF MODERN AIRTIGHT CONSTRUCTION LEAVING THE DOOR OPEN WILL HELP SPREAD WARMTH THROUGH THE REST OF YOUR HOME SAFETY Always keep children well away from the heater when it is alight as surfaces on radiant heaters can become very hot If children or aged and infirm persons might accidentally touc...

Page 12: ...sote and soot build up are inadequate draught smoking when the door is opened and a dull thud when the outside of the flue is tapped A blocked flue can be cleaned only by sweeping DO NOT USE CHEMICAL CHIMNEY CLEANERS To facilitate flue cleaning the firebox ceiling baffle should be lifted out See ASSEMBLY page 3 for instructions on re fitting the baffle correctly CLEANING THE HEATER Usually a wipe ...

Reviews: