CORNER HEARTHS

While the information in the previous section details the MINIMUM size of hearth
necessary to comply with the Safety Standards, it may be desirable to use a larger
hearth for æsthetic considerations. A particular example is when the heater is installed
diagonally in a corner. A neater appearance will result if the hearth is carried right into
the corner and is shaped as shown below. The chart facilitates calculation of the
MINIMUM dimensions required for hearths of this shape. The minimum allowable
values for dimension ‘E’ are given in the tables on page 4.

E

E

X

X

Y

Y

Special Corner
Hearth Arrangement

.

.

X

Y

NOTE: YOUR SPECIFIC MEASUREMENT FOR 

'E'  

MUST BE

ADDED TO 

'X' 

AND 

'Y'  

TO FIND THE APPROPRIATE

MINIMUM HEARTH DIMENSIONS.

SEE PAGE 4 FOR MINIMUM VALUES OF 

'E' .

MINIMUM DIMENSIONS

(Millimetres)

Australia

750

430

New Zealand

(hearth 50mm high)

New Zealand

(hearth flush)

Arcadia

Utopia

Utopia

Utopia

Arcadia

Arcadia

800

540

750

470

1050

730

1000

680

850

550

HEARTH CONSTRUCTION

In Australia the minimum hearth construction requirement is a 6mm fibre cement sheet.
It is usually fastened directly to the floor.

In New Zealand, the hearth will need the insulating qualities provided by two layers of
MICORE 160 (each 16mm thick), or one layer of WOODTEX (35mm thick). Both
these materials give adequate protection for solid timber or particle board flooring.
Alternatively, a reinforced concrete slab at least 50mm thick raised up from the floor on

7

Summary of Contents for ARCADIA

Page 1: ...ARCADIA UTOPIA UTOPIA Series 2 GRAND UTOPIA SOLID FUEL HEATERS INSTALLING AND OPERATING INSTRUCTIONS 585877 ...

Page 2: ...ou should approach your local Building Authority before commencing installation to establish whether you will require a Permit and whether you will need to meet extra requirements MASPORT radiant heaters have been tested to ensure that they will meet the appropriate safety Standard requirements if the instructions in this book are followed PLEASE ENSURE THAT ONLY COMPONENTS APPROVED BY MASPORT ARE...

Page 3: ...lign with the back edge of the top of the heater and the extension should fit snugly against the top casting Raise the heater into its upright position again taking care not to damage the floor Before fitting the firebox ceiling baffle first locate the four support lugs which will support it near the top of the firebox Insert the baffle into the firebox ensuring that the curved centre section is a...

Page 4: ...nts for a fireplace installation Finalise the installation position for your woodfire only after considering the necessary heater to wall distances see below and checking the practicability of installing the flue system through the ceiling and roof or wall As a guide the flue shielding and the 25mm clearance gap around it in the ceiling space will occupy a diameter of approximately 300mm and this ...

Page 5: ... 25 mm2 i e 15 000mm2 So if the effective length of each slot is 1m it will need to be 15mm wide Three types of shield are recommended Type Layers Spacing Clearance Factor A One 12mm 0 4 B One 25mm 0 3 C Two 12 12mm 0 2 Valid only for shields within 45 of vertical To find the reduced minimum distances multiply the figures in columns A B and E from the Table on page 4 by the appropriate clearance f...

Page 6: ...A G H J G l a ss W 360 min Wall Minimum dims for A are on page 4 See Notes below MINIMUM HEARTH EXTENSIONS mm WHEN THE REAR HEAT SHIELD IS FITTED Rear Heat Shield W B C D G H J Australia New Zealand New Zealand hearth flush hearth 50mm high Arcadia Utopia Arcadia Utopia Arcadia Utopia 855 635 300 165 150 335 525 1075 760 425 275 150 335 525 975 680 345 225 150 335 525 1165 980 550 275 155 430 615 ...

Page 7: ...X Y NOTE YOUR SPECIFIC MEASUREMENT FOR E MUST BE ADDED TO X AND Y TO FIND THE APPROPRIATE MINIMUM HEARTH DIMENSIONS SEE PAGE 4 FOR MINIMUM VALUES OF E MINIMUM DIMENSIONS Millimetres Australia 750 430 New Zealand hearth 50mm high New Zealand hearth flush Arcadia Utopia Utopia Utopia Arcadia Arcadia 800 540 750 470 1050 730 1000 680 850 550 HEARTH CONSTRUCTION In Australia the minimum hearth constru...

Page 8: ...Australia Not less than 18mm thickness of fibre cement board New Zealand Two sheets of MICORE160 or one sheet of WOODTEX 35 thick Ceramic tiles Trim moulding Recommended hearth constructions are FITTING A WATER COIL Water heating coils can be fitted to Arcadia and Utopia heaters The pipe attachment positions are shown below B Heater A B Arcadia Utopia 280 310 590 520 C Alternate flue position at r...

Page 9: ...apter 7 1985 except that the specified separation between the outside of the chimney and timber construction need not be complied with A flue pipe must be fitted right up the chimney and the space between the flue pipe and chimney must be ventilated at the top In Australia the area of this vent must be not less than 10 000mm2 while in New Zealand it is 13 000mm2 The vent must be fitted with means ...

Page 10: ...ing instructions will ensure satisfactory performance The use of wood with greater than 25 moisture is not permitted MAKE SURE THE MINIMUM HEATER TO WALL DISTANCES SHOWN ON PAGE 4 ARE ALWAYS MAINTAINED BETWEEN THE HEATER AND ANY HEAT SENSITIVE MATERIAL SUCH AS FURNITURE WINDOW DRAPES FUEL ETC DO NOT ATTEMPT TO BURN LIQUID FUELS OF ANY KIND LIGHTING UP Before lighting the first fire spread the sand...

Page 11: ...LED YOU MAY HAVE TO LEAVE A DOOR SLIGHTLY OPEN AND PERHAPS A WINDOW ELSEWHERE IN THE HOUSE IF YOUR HOME IS OF MODERN AIRTIGHT CONSTRUCTION LEAVING THE DOOR OPEN WILL HELP SPREAD WARMTH THROUGH THE REST OF YOUR HOME SAFETY Always keep children well away from the heater when it is alight as surfaces on radiant heaters can become very hot If children or aged and infirm persons might accidentally touc...

Page 12: ...sote and soot build up are inadequate draught smoking when the door is opened and a dull thud when the outside of the flue is tapped A blocked flue can be cleaned only by sweeping DO NOT USE CHEMICAL CHIMNEY CLEANERS To facilitate flue cleaning the firebox ceiling baffle should be lifted out See ASSEMBLY page 3 for instructions on re fitting the baffle correctly CLEANING THE HEATER Usually a wipe ...

Reviews: