Masibust VT7S12E User Manual Download Page 5

VIBRATION TRANSMITTER-VT7S12E 

Ref No: mVTD/om/201           

Issue No: 02

   

 

 

                                                                      

 

User’s Manual 

- 5 - 

2. INSTALLATION 

 

Mounting method: 

DIN Rail mounting 

To install the controller select a location where: 
 

 

no one may accidentally touch the terminals 

 

mechanical vibrations are minimal 

 

corrosive gas is minimal 

 

temperature can be maintained at about 25

˚C to 35˚C and the fluctuation is minimal 

 

no direct radiant heat is present 

 

no magnetic disturbances are caused 

 

no wind blows against the terminal board 

 

no water splashed 

 

no flammable materials are around 

 

  Turn off the power to the controller before installing it on the Din Rail because there is a possibility of electric shock

 

 
How to connect wires: 

 

             Before carrying out wiring, turn off the power to the controller and check that the cables to be connected are not 

alive with a tester or the like because there is a possibility of electric shock. 
 

 

NOTE:

 

 

o

 

All wiring must confirm to appropriate standards of good practice and local codes and regulations. Wiring must be suitable 
for Voltage, Current and temperature rating of the system. 

o

 

Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an insulating 
transformer  into  the  primary  side  of  the  line  and  use  a  line  filter  on  the  secondary  side.  Do  not  place  the  primary  and 
secondary power cables close to each other. 

o

 

Use repeater after each set of 32 instruments connected in RS-485 Communication. 

o

 

Unused terminals should not be used as jumper points as they may be internally connected, which may cause damage to 
the unit. 

 

CAUTION:

 

 
High voltage transients may occur when switching inductive loads such as some contactors or solenoid valves. Through the internal 
contacts, these transients may introduce disturbances which could affect the performance of the instrument. 
For this type of load it is hi

ghly recommended that a “snubber” is connected across the normally open contact of the relay switching 

though  load.  The  snubber  recommended  consists  of  a  series  connected  resistor/capacitor  (typically 

15nF/100  Ohms

).  A  snubber 

will also prolong the life of the relay contacts. A snubber should also be connected across the output of a trip output to prevent false 
triggering under line transient conditions.

 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for VT7S12E

Page 1: ...02 User s Manual 1 USER MANUAL VT7S12E VIBRATION TRANSMITTER Masibus Automation Instrumentation Pvt Ltd B 30 GIDC Electronics Estate Sector 25 Gandhinagar 382044 Gujarat India 91 79 23287275 79 91 79...

Page 2: ...vironmental specification 7 3 6 Output relay specification 7 3 7 Analog output specification 7 3 8 Rs 485 communication specification optional 7 3 9 Buffer output specification 7 3 10 Signal isolation...

Page 3: ...Register 24 Table 20 Modbus Parameter Details for Calibration Register 24 Table 21 Modbus Parameter Details for Read Output Status Register 25 Table 22 Input Type Selection Table 25 Table 23 Relay Log...

Page 4: ...hould any errors or omissions come to your attention however please inform Masibus Sales office or sales representative Under no circumstances may the contents of this manual in part or in whole be tr...

Page 5: ...ent and temperature rating of the system o Provide power from a single phase instrument power supply If there is a lot of noise in the power line insert an insulating transformer into the primary side...

Page 6: ...1KHz 2 5KHz 10KHz Filter Accuracy 10 of Cut off Frequency Measuring parameter Acceleration Velocity Displacement Measuring Range 1 Acceleration 0 50 g RMS peak derived 2 Velocity 0 100 mm s RMS peak...

Page 7: ...CRC Check 3 9 Buffer output specification No of output Two Output Impedance 100 Ohms Frequency Range 0 5 Hz to 10KHz Accuracy 0 25 of Full Range 3 10 Signal isolations and insulation specification Iso...

Page 8: ...DESCRIPTION MENU ENTER KEY It is used to enter in the sub menu various levels and save the parameters to nonvolatile memory when user setting a proper data by Increment and shift key for parameter con...

Page 9: ...VIBRATION TRANSMITTER VT7S12E Ref No mVTD om 201 Issue No 02 User s Manual 9 6 CONNETION DIAGRAM Figure 2 Connection Diagram of VT7S12E...

Page 10: ...D om 201 Issue No 02 User s Manual 10 7 MENU LAYOUT 7 1 Flow Diagram Vibration Transmitter VT7S12E has a number of software parameters which may or may not be required depending on your particular app...

Page 11: ...LH rLGP SCAn Srno bAud PrSt tout rtos rttP rtdr rtmp CAL pwd 0000 0000 CALZ CALS rtrZ rtrS Procedure for changing setting different values to different channels in all levels is shown in the level 1 H...

Page 12: ...key DATA window shows LVL1 LvL1 message Press MENU key again DATA window shows pwd PWD message press increment key twice to select password and then press MENU key to enter into Level 1 DATA window s...

Page 13: ...et to Al Rldl rLdL Relay Delay Applicable for All Relay 1 to 99 seconds 1 second for All Relay Rlos rLoS Relay Open sensor Applicable for All Relay up Dn UP Down 0 DOW N 1 UP Up Scale for All Relay Rl...

Page 14: ...ll be assigned channel wise and all assignments are remain fixed And Relay type Example Table 10 Relay as Control Output Configuration Detail For Relay functionality Refer Relay outputs Chapter 8 3 LE...

Page 15: ...rd Rtdr rtdr Retransmission direction Dir rev 1 dir 0 rev 1 For Both Output Card Rtmp rt mp Retransmission mapping See Table 8 Rtrd rtrd Retransmission Channel Value Max Min 1 Max 0 Min 1 For Both Out...

Page 16: ...nsor type selected Rtr Z rtr Z Retransmission voltage and current Zero calibration Depending on Retransmission type selected Rtr S rtr S Retransmission voltage and current Span calibration Depending o...

Page 17: ...crosses the set point For heating control the output is on when the temperature is below the set point and off above set point Since the temperature crosses the set point to change the output stage t...

Page 18: ...tch No Lamp Off Steady Off Steady Off Off Relay Off On Off On Off Off Trip Lamp Off Steady Off Off Steady Off Relay Off On Off Off On Off Alarm al2 Momemtary alarm when in abnormal condition ack not p...

Page 19: ...dy Off Steady Steady Off Off Relay Off On Off On Off Off Off Trip Lamp Off Steady Off Off Steady Steady Off Relay Off On Off Off On On Off Alarm al2 Maintained alarm when in abnormal condition ack is...

Page 20: ...condition after abnormal has already occurred means it remains in the previous state If previous state is ON then it will remain ON and the same case for OFF condition Pressing Shift Decrement key fo...

Page 21: ...he DATA window to indicate that it is doing the necessary calculations Depending on the situation this process may take few seconds to calibrate Zero and Span calibration is over In case the controlle...

Page 22: ...us Parameter Details for Process Value Modbus values for OPEN OVER UNDER and SKIP Conditions Table 18 Details of abnormal Conditions of Process Value CODE NAME Function 01 Illegal function The functio...

Page 23: ...0029 INT R W 30 Range Low CH 2 40030 INT R W 31 Range Low CH 3 40031 INT R W 32 Range Low CH 4 40032 INT R W 33 Decimal Point CH 1 40033 INT 0 3 R W 34 Decimal Point CH 2 40034 INT 0 3 R W 35 Decimal...

Page 24: ...AO Card 1 40095 INT 0 1 R W Table 39 96 Retransmission Value AO Card 2 40096 INT 0 1 R W 98 Password 40098 INT 0 9999 R W 99 Over Limit 40099 INT 0 10 R W 100 Under Limit 40100 INT 0 10 R W 101 Digit...

Page 25: ...nput Type I P no Type Display Zero Span Resolution Acceleration RMS 1 A rm 0 50 0 0 1 Acceleration PEAK 2 A pk 0 50 0 0 1 Acceleration PEAK PEAK 3 A pp 0 50 0 0 1 Velocity RMS 4 V rm 0 100 0 0 1 Veloc...

Page 26: ...tch selection Modbus Index Parameter Value Modbus Index Parameter Value Modbus Index Parameter Value 0 Low ON 0 High Very High 0 OFF 1 High ON 1 Low Very Low 1 ON 2 High LOW Table 34 Baud Rate for Com...

Page 27: ...l display readings above 5 of display range then after it will show OVER UNDR message until value crosses maximum value of Sensor range OVER UNDER condition is applicable for RTD input types only Proc...

Page 28: ...CTION OPEN OVER ERROR 4 20 mA PV UP DIR 21 6 20 8 PV DOWN REV 20 8 3 2 PV UP REV 2 4 3 2 PV DOWN DIR 2 4 20 8 Table 41 Retransmission Output during Open Over Condition NOTE For Retransmission output t...

Page 29: ...ransmitter power follow the measures in the procedure below If a problem appears complicated contact our sales representative Masibus Automation Instrumentation Pvt Ltd Customer Support Division B 30...

Reviews: