Model: CDU-LCD
Doc. Ref. no.:- mMP/om/601
Issue no. 00.06
User’s Manual
Page 23 of 32
40044
Alarm Low
Set Alarm Type for Alarm LOW
0 : HI(High)
1 : LOW(Low)
2 : DIS(Disable)
LOW
40048
Band
Set band for data logging
0 to 100 For Pa - 0.1 Pascal Resolution
20
40051
Differential
Pressure
High range
It is a Differential Pressure High range for display.
0 to 5000 For Pa
– 0.1 Pascal Resolution
1250
40052
Differential
Pressure
Display
Range
Set Display Range For Differential Pressure Input
Unidirectional/Bidirectional
0: UN.DR
1: BI.DR
UN.DR
40053
Sensor
Break
Set Sensor Break Value
0 : MIN
(Display minimum value of Differential Pressure
range)
1 : LAST
(Display Last value of parameter in CDU)
2 : MAX
(Display Maximum Value of Differential
Pressure range)
LAST
40054
Pressure
Lower Limit
Set Pressure Lower Limit. Below this value
pressure will be displayed 0.
0.0 to 10.0
0.0
Table 10
8.6 OUT
40071
Source ID
Source ID
1 to 9999
1
40072
Destination /
Slave
ID
Destination ID DNP3 and Slave ID for modbus
1 to 247
2
40073
Baud Rate
Set Serial Communication Baud Rate
0 : 9.6K (9600 bps)
1 : 19.2K (19200 bps)
2 : 38.4K (38400 bps)
9.6K
40074
Buzzer Delay It is a delay time to Buzzer ON.
0 to 3600 Sec
30
40075
Buzzer
Status
Set Enable or Disable For Audible Process value
violation
0 : DIS
1 : EN
EN