RETRAMISSION OUTPUT TABLE FOR OPEN /OVER /UNDER CONDITION (Optional):
Table 64 Retransmission Output during Open/Over/Under Condition
RETRASMI
SSION
VARIABLE
SCALE ACTION OPEN
OVER
UNDER
ERROR
4-20mamp
PV
UP
DIR
20.8
Holds the last
value of
retransmisison
o/p
Holds the last
value of
retransmisison
o/p
-
PV
DOWN
REV
20.8
Holds the last
value of
retransmisison
o/p
Holds the last
value of
retransmisison
o/p
-
PV
UP
REV
3.2
Holds the last
value of
retransmisison
o/p
Holds the last
value of
retransmisison
o/p
-
PV
DOWN
DIR
3.2
Holds the last
value of
retransmisison
o/p
Holds the last
value of
retransmisison
o/p
-
NOTE: -
1) For Retransmission output type 0-20mamp, 0-10v, 1-5v and 0-5v also applicable
according to above table.
2) Also, 0-20mamp, 0-10v and 0-5v minimum output value will be 0mamp and 0v