background image

     DANGER

4.3.

A.C. Connection

This connection is made through the power terminal board
(fig.14, ref. 1). Remove the main panel to gain access to
the terminal strip as shown on fig. 13.

This range includes the possibility of use both at 120V
60Hz and 240V 60Hz.
For this reason it is possible to make two types of
connections (and use), according to the following configu-
rations.

1

- Parallel configuration: in this configuration there is a

single output at 120V between points P

1

 and F

2

,

connecting the outputs of the alternator (P

1

, F

1

, P

2

, F

2

)

as shown in the diagram in fig. 13 ref. 2.

2

- Serial connection; in this configuration it is possible

to use a voltage of 240V between points P

1

 and F

2

, as

shown in the diagram in fig. 13 ref 1.

In serial connection, power can be picked up both at 120
V between points F

1

 - F

2

 and P

1

 - P

2

 and at 240 V between

points P

1

 and F

2

 at the same time, as shown in the

diagram in fig. 15 ref. 3.

If the serial connector (fig. 15 ref. 3) is used to draw
a  voltage of 120V 60Hz the current drawn off must
not exceed 50% of the rated current.

- Ensure that the sum of the loads to be supplied does not

exceed the nominal power of the electric generator.

- The gen-set is equipped with a circuit breaker in order

to cut off the  output voltage in case of overload or short
circuit.

4.4.

Generator - Main switching

A switch should be placed in-line to switch generator to
shore power. The switch should be dimensioned according
to the size of the loads: a general diagram is shown in fig.
17.

5.   LIFTING

To lift the generator, use ONLY the provided lifting points.

Hooking and/or lifting from any point other than the
provided lifting point could damage the generator
and cause a dangerous situation.

12

Summary of Contents for Marine IS 9.5

Page 1: ...IS9 5 13501 INSTALLATION MANUAL ...

Page 2: ...Fig 1 Fig 2 1 2 Fig 3 Fig 4 2 32 7 8 31 1 1 16 3 8 22 3 8 3 3 3 5 32 7 8 27 1 8 2 2 3 8 MAX 40 MAX 40 MAX 40 MIN 12 MIN 8 M AX 80 MIN 13 5 IS9 5 ...

Page 3: ...Fig 6 3 Fig 6 MAX 40 MAX 40 MIN 12 MIN 8 M A X 8 0 MIN 13 5 IS9 5 MAX 40 MIN 6 MAX 40 MIN 12 MIN 8 MAX 40 IS9 5 MAX 16 6 MIN 13 5 M A X 8 0 IS9 5 MIN 6 MAX 40 MIN 12 MIN 8 MAX 40 MAX 16 6 MIN 12 M A X 8 0 MIN 13 5 ...

Page 4: ...Fig 9 1 Fig 8 Fig 12 Fig 11 Fig 10 1 2 3 4 Anti siphon valve 4 ...

Page 5: ...Fig 14 Fig 13 1 2 1 3 Fig 15 1 5 ...

Page 6: ...Fig 16 Fig 17 GEN LOAD MAIN 1 6 ...

Page 7: ...Fig 18 IS9 5 7 ...

Page 8: ... that significant attention must be paid in order to prevent serious danger which could lead to injury or death A condition which may occur during the lifetime of a product system or plant that has the potential for human injury damage to property damage to the environment or economic loss Indicatesthatparticularattentionmustbepaidinordertopreventseriousconsequenseswhich could reselt to tangible g...

Page 9: ...SYSTEM SUPPLIED BY MASE HASBEENMODIFIEDTOPREVENTSOLIDOBJECTS FROMENTERINGTHESYSTEMANDBLOCKINGIT IFOTHERMATERIALSAREUSED MORECAREAND MOREFREQUENTCLEANINGISNECESSARY The baffle system might cause the following problems a If installed with the slots facing the bow In this case during navigation and with the electric generator off pressure is accumulated in the water infeed duct which might cause the ...

Page 10: ...5 Components The raw water intake system must be separate from the one for the engines propelling the boat 1 Direct raw water intake 1 2 If the unit is installed more than 40 above the water line a check valve should be fitted after the sea intake fig 8 ref 1 to prevent the water circuit emptying when the motor is off If this empties the rotor of the water pump might be damaged during start up for...

Page 11: ...e end of the connection cable in the socket placed on the inner board of the genset and the opposite end in the remote control panel fig 16 ref 1 WARNING DANGER remain empty to allow air to pass through when the unit is switched off see fig 9 Itisrecommendedthatthedrainhosefromtheanti siphon valvebefedintothebilge assmallamountsofwatermight bedrainedthroughitduringnormaloperation Thecooling circui...

Page 12: ...on power can be picked up both at 120 VbetweenpointsF1 F2 andP1 P2 andat240Vbetween points P1 and F2 at the same time as shown in the diagram in fig 15 ref 3 If the serial connector fig 15 ref 3 is used to draw a voltage of 120V 60Hz the current drawn off must not exceed 50 of the rated current Ensurethatthesumoftheloadstobesupplieddoesnot exceed the nominal power of the electric generator The gen...

Reviews: