Page 4
Optima 820 Series
1.3 General Description
The Optima 820 Series (model numbers MPD 820XXX) is a family of 48 power distribution units (PDUs) designed for use
with a single
-phase
supply power of either 120 Vac, 110–240 Vac, or 200–240 Vac.
Each PDU receives mains power through an inlet located at the rear. Power is distributed to all outlets on one or two
branches depending on the model. A variety of inlet and outlet connectors is available.
All models include a circuit breaker, indicator, surge suppression, and Marway’s RCM
™
networking control system to
provide individual outlet switching over Ethernet
®
. Additionally, three options of inlet power monitoring with digital display,
a remote on/off/EPO control bus, and an integral EMI filter are available in a variety of combinations.
All models are constructed of a steel chassis, and designed for fixed mounting within a 1U rack space in an EIA-310
compliant rack enclosure.
This documentation is about the hardware elements of the Optima 820 Series of PDUs. For detailed
information about the software, you’ll need the
Optima RCM User Guide : Software and Basic
Controls Reference
1.4 Product Models
&
Ratings
Models are primarily organized by what type of power inlet they have. Then by the outlet configurations. All models have
one unswitched utility outlet on the front panel, and eight software switched outlets on the rear panel. Marway’s Standard
Products Catalog includes more detailed tables with exact model number configurations with inlets, outlets, and options
identified.
Group
Models*
Mains Inlet
Inlet Rating
Outlets
Outlet Ratings
Group 1
MPD 820001
and
MPD 820101
NEMA 5-15P
120 Vac, 50/60 Hz
12 A continuous
(15 A maximum)
NEMA 5-15R
•
12 A per outlet (15 A max)
•
12 A unit total (15 A max)
Group 2
MPD 820002
and
MPD 820102
NEMA 5-20P
120 Vac, 50/60 Hz
16 A continuous
(20 A maximum)
NEMA 5-20R
•
16 A per outlet (20 A max)
•
16 A unit total (20 A max)
Group 3
MPD 820003
and
MPD 820103
NEMA L5-20P
120 Vac, 50/60 Hz
16 A continuous
(20 A maximum)
NEMA 5-20R
•
16 A per outlet (20 A max)
•
16 A unit total (20 A max)
Group 4
MPD 820004
and
MPD 820104
NEMA L6-20P
200–240 Vac, 50/60 Hz
16 A continuous
(20 A maximum)
IEC C13
•
10 A per outlet (10 A max)
•
16 A unit total (20 A max)
Group 5
MPD 820005
and
MPD 820105
IEC C20
110–240 Vac, 50/60 Hz
16 A continuous
(20 A maximum)
IEC C13
•
10 A per outlet (10 A max)
•
16 A unit total (20 A max)
Continued next page.