Page 14
Optima 820 Series
5
Specifications
Remote EPO (optional)
•
Panel connector: AMP #1-480304-0, 250 Vac, 4 A maximum.
•
Mating cable connector: AMP #1-480305-0.
•
All outlets other than J9 are managed by the Remote Control Bus.
•
J9 outlets are always powered relative to the Main Breaker state
(regardless of remote state).
Pin 3 : Return
Power On
Power Off,
EPO Active
Pin 2 : Disable
Pin 1 : Enable
J1
Marway UCP, or
customer supplied circuit
Remote On
EPO Override
Enable Outlet
Groups B & C
Marway Optima PDU
Optima Remote EPO Circuit
Inlet Voltage Options
•
120 Vac, 50/60 Hz, single phase
•
200–240 Vac, 50/60 Hz, single phase
•
100–240 Vac, 50/60 Hz, single phase
• All voltages are listed as nominal input sources.
Current Capacity Options
•
12 A continuous load / 15 A maximum
•
16 A continuous load / 20 A maximum
•
24 A continuous load / 30 A maximum
•
Based on NEC regulations, traditional load ratings are de-rated to
80% for continuous duty. For example, a traditional 30 A maximum
rating is now interpreted and labeled as a 24 A continuous duty
rating. Optima current ratings are shown with continuous/maxi
-
mum rating values.
Overload Protection (standard)
•
All models include a two-pole UL 489 circuit breaker.
•
12/15 A models are wired with both line and neutral passing
through the circuit breaker.
•
16/20 A models are wired with both line and neutral passing
through the circuit breaker.
•
24/30 A models in Groups 6 and 8 use a 15 A breaker with the
main line branched to each pole of the breaker (creating two
15 A sub-circuits).
•
24/30 A models in Group 7 use a 20 A breaker with the main
line branched to each pole of the breaker (creating two 20 A
sub-circuits).
Surge Suppression (standard)
• All models include a thermally protected varistor.
•
120 Vac models have a single-pulse energy rating of 100 joules.
•
240 Vac models have a single-pulse energy rating of 170 joules.
•
All models have a peak surge current rating of 10,000 A for a
single pulse 8x20µs wave.
Environment
•
Operating Temperature: 32°F to 122°F
•
Maximum Altitude: 6,562 feet
•
Relative Humidity: 5% to 85% non-condensing
EMI Filter (optional)
•
120 Vac models have < 0.5 mA leakage.
•
240 Vac models have < 1.0 mA leakage.
100
90
80
70
60
50
40
30
20
10
0
0.01
0.1
1
10
30
db
Typical Insertion Loss
(closed 50 Ohm system)
Frequency in MHz
Common Mode
Differential Mode
Networking
Ethernet 10/100T
•
IPv4: DHCP, Static
Web Interface
•
HTTP, HTTPS
Command Line Interface
•
Telnet, SSH, RS-232
SNMP
•
v2/v3
•
Access to power data, alarms,
outlet switching
Alerts
• Email over SMTP
• SMS over SMTP
•
SNMP v2/v3 Traps
Scriptability
• RESTful API
•
Telnet/SSH
• SNMP
Other Protocols
•
SNTP, SNMP, FTP