21
4.4.2 Dial switch setting
When the battery is connected to the PC host, the address should be set to 0 to communicate with the PC host
computer;
When the battery is used in parallel, set the address through the dial switch on the battery to distinguish
different addresses. It is necessary to avoid setting the address to the same.
When the battery communicates with the inverter (or controller), the address of the corresponding battery
connected to the inverter (controller) must be set to 1, otherwise the communication cannot be established
Dial switch interface
The details of setting method is shown in the table below
:
NO.
Moudle
Address
BMS Module ID
ID Arrangement
1#
2#
3#
4#
1
0x01
1
ON
OFF
OFF
OFF
2
0x02
2
OFF
ON
OFF
OFF
3
0x03
3
ON
ON
OFF
OFF
4
0x04
4
OFF
OFF
ON
OFF
5
0x05
5
ON
OFF
ON
OFF
6
0x06
6
OFF
ON
ON
OFF
7
0x07
7
ON
ON
ON
OFF
8
0x08
8
OFF
OFF
OFF
ON
9
0x09
9
ON
OFF
OFF
ON
10
0x0A
10
OFF
ON
OFF
ON
11
0x0B
11
ON
ON
OFF
ON
12
0x0C
12
OFF
OFF
ON
ON
13
0x0D
13
ON
OFF
ON
ON
14
0x0E
14
OFF
ON
ON
ON
15
0x0F
15
ON
ON
ON
ON
0
0x00
0
OFF
OFF
OFF
OFF
5 Troubleshooting
Check the indicators on the front of the battery to determine the status of the battery pack. A warning state is
triggered when a condition, such as voltage or temperature, is outside battery’s rating. When the battery
pack status falls outside of set limits, it enters a warning state. When a warning is reported, turn off the DC
source immediately.
Use the monitoring software to identify the cause of the warning.
Warning Alarms
Battery Over Voltage
Battery Under Voltage
Battery Over Temperature
Battery Under Temperature
Battery Discharge Over Current
Battery Charge Over Current