background image

MAR7000 

11 

1/2013, P/N 01757 Rev. B

Max Info Frames

 (view only) is the maximum 

number of information frames (data packets) that 

a controller may send out before it must pass the 

token.
For 

IP

 and 

IP Foreign Device

 communications, 

consult with the system administrator for the 

appropriate settings for the IP Address, Subnet 

Mask, Gateway, and UDP Port.

Ethernet

 communications are essentially plug-

and-play, and the MAC address is not changeable.

(Advanced) CO

2

 Sensor

 

CO2 SENSOR

SENSOR INFO

 

CO2 SENSOR INFO

MODEL: T6615
SUB VOL: A15
SW DATE: 090217
S/N: AB00011759
CO2: 873
ELEVATION: 0
STATUS: NORMAL

Set the desired CO

2

 setpoint under the Setpoints 

menu. See 

Setpoints on page 16

.

For maximum sensor accuracy, 

enter the eleva-

tion (altitude) above sea level

 of the building’s 

location. (The default value is 0.) Elevation for any 

particular location can be found at such sources as 

www.earthtools.org

. (For very tall buildings, the 

upper floors would have a higher elevation than 

lower floors.)
After power is first applied or the FlexStat is 

restarted, the sensor goes through a 

warm-up 

for 

approximately half a minute. During the time the 

sensor count will be 0 ppm and the Status line 

would display WARMUP instead of NORMAL.
The 

sensor and its firmware

 are identified by the 

model, the compilation subvolume (SUB VOL), 

compilation date (SW DATE in yymmdd format), 

and serial number.
NOTE:  With the CO

2

 sensor enabled, a trend log 

is automatically generated. See 

Trend 

Viewer on page 16

.

The CO

2

 models have a patented self-calibration 

technique designed to be used 

in applications 

where concentrations will drop to outside ambi-

ent conditions (approximately 400 ppm) at least 

three times in a 14 day period,

 typically during 

unoccupied periods.

(Advanced) Date/Time

 

DATE/TIME

DATE:

TIME: 1:43:59 PM
UTC OFFSET: 300
DST ENABLE: TRUE
DST AUTO: TRUE
DST START:
>2ND SUN MAR    2:00 AM

APRIL 11 2009

If the MAR7000 is used in a BACnet network with 

UTC (Coordinated Universal Time) 

synchroniza-

tion (via broadcasting or addressing a single ther-

mostat) set the UTC Offset value. The UTC Offset 

value is in minutes and corresponds to the distance 

of the local time zone to the zero degree meridian. 

For example, USA/Canada Pacific Standard Time 

(8 hours) = 

480

 minutes and USA/Canada Eastern 

Standard Time (5 hours) = 

300

 minutes.

In stand-alone operation or networks that do not 

have UTC broadcasts, setting this value is not nec-

essary.
NOTE:  The BACnet standard for this offset 

value is: “The time zones to the west 

of the zero degree meridian shall be 

positive values, and those to the east 

shall be negative values.” The value is in 

minutes

, not hours.

For areas that observe 

DST (Daylight Saving 

Time)

, select True/On for DST ENABLE and DST 

AUTO. The

 

DST period is currently the second 

Sunday of March through the first Sunday of 

November, but these rules can be changed in the 

menu if the official period changes or if the in-

stalled location needs a schedule adjustment for 

better operation.
NOTE:  If DST is enabled but the Auto setting is 

not, the actual calendar dates (instead of 

using the general rules) will need to be 

entered every year.

Summary of Contents for MAR7000

Page 1: ...r data selection and entry Built in factory tested libraries of configurable application control sequences Integral energy management control with deadband heating and cooling set points and other adv...

Page 2: ...backplates at a later time if desired Attractive white plastic case Supply Voltage 24 VAC 20 15 Class 2 Supply Power 13 VA not including relays Connections Wire clamp type terminal blocks 14 22 AWG c...

Page 3: ...utes operational and 10 minutes maximum accuracy This model uses Automatic Background Calibration Logic or ABC Logic a patented self calibration technique designed to be used in applications where con...

Page 4: ...wall and away from heat sources sunlight windows air vents and air circulation obstructions e g curtains or furniture Install it where the motion sensor will have unobstructed view of the most typica...

Page 5: ...both switches are Off left down 10K 0 12 V Input Pull Up Switches EOL Switches ON OFF Pushed Left Pushed Right IN2 IN3 IN4 IN7 IN8 IN9 1 2 3 4 5 6 3 4 3 4 IN4 5 6 10K 0 12 V 5 6 IN3 7 8 7 8 IN2 7 8 E...

Page 6: ...he MAR7000 s output capacity Maximum output current is 1 A for individual relays 24 VAC VDC or a total of 1 5 A per bank of 3 relays relays 1 3 and 4 6 Relays are NO SPST Form A B A IN4 IN3 GND IN2 Co...

Page 7: ...permanently change the setpoint for occupied mode go to the Setpoints section under the Main Menu In the Setpoints menu heating cooling setpoints setbacks and deadband can be changed with if required...

Page 8: ...d Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE TIME DEVICE INPUTS LIMITS The Advanced Menu displays various submenus Not all submenus can be seen on the screen at one time Scroll up or dow...

Page 9: ...ll window To change the schedule with the default setting after an initial detection motion must also be detected at least once during the second quarter of the window approximately minutes 8 15 third...

Page 10: ...will attempt to locate when polling for master devices on the local network To avoid possible communication issues with the network the Max Master number should be the lowest number needed for that ne...

Page 11: ...Viewer on page 16 The CO2 models have a patented self calibration technique designed to be used in applications where concentrations will drop to outside ambi ent conditions approximately 400 ppm at l...

Page 12: ...menu items accessible at the various levels are shown in the following chart NOTE Changes in security levels and or passwords take effect when the current Administrator log in has timed out Log ins l...

Page 13: ...Trend Logs TRUE TREND LOGS TREND 1 TREND 2 TRUE TREND 3 FALSE TREND 4 FALSE TREND 5 FALSE TREND 6 FALSE TREND 7 FALSE TREND 1 SPACE TEMPERATURE LOG OBJECT REF AI1 LOG ENABLE TRUE INTERVAL MINS 10 STO...

Page 14: ...are Fahrenheit tem perature values on the display change in whole degree increments by default and Celsius values change in 0 5 increments Changing the default No to Yes will show tenths of a degree v...

Page 15: ...y separately in the Individual Days menu five entries NOTE The last overlapping entry overrides any other For example suppose the WEEKDAYS menu is used to set all weekdays for 7 00 AM ON and 5 00 PM O...

Page 16: ...eduled setpoint When the time is set to 0 the override state will last until the next schedule change Motion Override on this menu is the amount of time in minutes detected motion will temporar ily pl...

Page 17: ...ing the pointed object into the socket from the back side can be helpful When installing the cover it may be helpful to ap ply more pressure toward the bottom of the cover Replace the backplate NOTE W...

Page 18: ...al power up or restart the motion occupancy sensor requires about 30 seconds before it will begin responding to motion The motion occupancy sensor initiates override only during off times in the sched...

Page 19: ...e 5 Check baud rate see Advanced Communications BACnet on page 10 Reduce the Max Master number down to the minimum needed for that network see Advanced Communications BACnet on page 10 See Wiring Issu...

Page 20: ...No voltage may indicate a bad connection or simply no active network NOTE Wiring must be adequate to avoid excessive voltage drop on long runs Allow plenty of cushion in measurements A meter may be t...

Page 21: ...urns all object values to their relinquished defaults until they are updated by the MAR7000 s programs restarts the controller s Control Basic programs and leaves configuration and programming intact...

Page 22: ...ion and Basic Operation 7 Home Main Menu and Override Screens 7 Navigation 7 Room Temp Setpoint Adjustment 7 Main Menu and Settings 7 H C Fan Occupancy and Override 7 Configuration General 8 Advanced...

Reviews: