Marvair MAR7000 Product Data Sheet Download Page 4

MAR7000 

1/2013, P/N 01757 Rev. B

Connections and Wiring

Wiring Considerations

•  Because of the many connections (power, 

network, inputs, outputs, and their respective 

grounds or switched commons), be sure 

wiring is well planned before installation of 

conduit!

•  Make sure that conduit for all wiring has 

adequate diameter for all necessary wiring. 

Using 1-inch conduit and junction boxes is 

recommended! Use external junction boxes 

above the ceiling or in another convenient 

location as needed to make connections that 

run to the MAR7000’s junction box.

•  To prevent excessive voltage drop, 

use a 

conductor size that is adequate for the wiring 

length! Allow plenty of “cushion” to allow 

for transient peaks during startup.

•  Using multiple conductor wires for all inputs 

(e.g., six conductor) and outputs (e.g., 12 

conductor) is recommended. Grounds for all 

the inputs can be combined on one wire.

 CAUTION

To avoid damage from ground loops and 
other communication issues in networked 
MAR7000s, correct phasing on MS/TP 
network and power connections on ALL the 
networked controllers is critically important.

 CAUTION

•  This thermostat is for 24 VAC applications only. 

Do not use on voltages over 30 VAC.

•  All installation and wiring must conform to local 

and national electrical and building codes.

•  Use this thermostat only as described in this 

manual.

Mounting

For optimum temperature sensor performance, 

the MAR7000 must be mounted on an interior 

wall and away from heat sources, sunlight, 

windows, air vents, and air circulation 

obstructions (e.g., curtains or furniture). Install it 

where the motion sensor will have unobstructed 

view of the most typical traffic area

.

If replacing an existing thermostat, label wires as 

needed for reference when removing the existing 

thermostat.

 CAUTION

Installing a 6-input model on a (powered) 3-in-
put backplate (see page 5) will permanently 
damage the controller.
To prevent mounting screw heads from touching 
the circuit board in the thermostat, use only the 
supplied mounting screws. Using screws other 
than the type supplied may damage the controller.

1.  Complete rough-in wiring at each location 

prior to thermostat installation. Cable 

insulation must meet local building codes.

2.  Push in on the tabs (two on top and bottom), 

and pull the cover away from the backplate 

(mounting base).

3.  Route the wiring through the backplate.
4.  With the embossed UP toward the ceiling, 

fasten the backplate directly to a 

vertical

 2 x 4 

inch wall handy-box.

5.  Make the appropriate connections to the 

terminal blocks. (See 

Connections and Wiring 

on page 4

.)

6.  Seal the hole for wires behind the mounting 

base with non-flammable insulation or putty.

7.  Snap the MAR7000 cover over the backplate 

while being careful not to pinch or dislodge 

any wiring.

Installation

 WARNING

ALWAYS TURN OFF POWER AT THE MAIN 
POWER SUPPLY BEFORE INSTALLING, 
CLEANING, OR REMOVING THE MAR7000. 
TURN OFF POWER AT THE MAIN SERVICE PANEL 
BY REMOVING THE FUSE OR SWITCHING THE 
APPROPRIATE CIRCUIT BREAKER TO THE OFF 
POSITION BEFORE REMOVING AN EXISTING 
THERMOSTAT OR INSTALLING A NEW ONE.

Summary of Contents for MAR7000

Page 1: ...r data selection and entry Built in factory tested libraries of configurable application control sequences Integral energy management control with deadband heating and cooling set points and other adv...

Page 2: ...backplates at a later time if desired Attractive white plastic case Supply Voltage 24 VAC 20 15 Class 2 Supply Power 13 VA not including relays Connections Wire clamp type terminal blocks 14 22 AWG c...

Page 3: ...utes operational and 10 minutes maximum accuracy This model uses Automatic Background Calibration Logic or ABC Logic a patented self calibration technique designed to be used in applications where con...

Page 4: ...wall and away from heat sources sunlight windows air vents and air circulation obstructions e g curtains or furniture Install it where the motion sensor will have unobstructed view of the most typica...

Page 5: ...both switches are Off left down 10K 0 12 V Input Pull Up Switches EOL Switches ON OFF Pushed Left Pushed Right IN2 IN3 IN4 IN7 IN8 IN9 1 2 3 4 5 6 3 4 3 4 IN4 5 6 10K 0 12 V 5 6 IN3 7 8 7 8 IN2 7 8 E...

Page 6: ...he MAR7000 s output capacity Maximum output current is 1 A for individual relays 24 VAC VDC or a total of 1 5 A per bank of 3 relays relays 1 3 and 4 6 Relays are NO SPST Form A B A IN4 IN3 GND IN2 Co...

Page 7: ...permanently change the setpoint for occupied mode go to the Setpoints section under the Main Menu In the Setpoints menu heating cooling setpoints setbacks and deadband can be changed with if required...

Page 8: ...d Menu ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE TIME DEVICE INPUTS LIMITS The Advanced Menu displays various submenus Not all submenus can be seen on the screen at one time Scroll up or dow...

Page 9: ...ll window To change the schedule with the default setting after an initial detection motion must also be detected at least once during the second quarter of the window approximately minutes 8 15 third...

Page 10: ...will attempt to locate when polling for master devices on the local network To avoid possible communication issues with the network the Max Master number should be the lowest number needed for that ne...

Page 11: ...Viewer on page 16 The CO2 models have a patented self calibration technique designed to be used in applications where concentrations will drop to outside ambi ent conditions approximately 400 ppm at l...

Page 12: ...menu items accessible at the various levels are shown in the following chart NOTE Changes in security levels and or passwords take effect when the current Administrator log in has timed out Log ins l...

Page 13: ...Trend Logs TRUE TREND LOGS TREND 1 TREND 2 TRUE TREND 3 FALSE TREND 4 FALSE TREND 5 FALSE TREND 6 FALSE TREND 7 FALSE TREND 1 SPACE TEMPERATURE LOG OBJECT REF AI1 LOG ENABLE TRUE INTERVAL MINS 10 STO...

Page 14: ...are Fahrenheit tem perature values on the display change in whole degree increments by default and Celsius values change in 0 5 increments Changing the default No to Yes will show tenths of a degree v...

Page 15: ...y separately in the Individual Days menu five entries NOTE The last overlapping entry overrides any other For example suppose the WEEKDAYS menu is used to set all weekdays for 7 00 AM ON and 5 00 PM O...

Page 16: ...eduled setpoint When the time is set to 0 the override state will last until the next schedule change Motion Override on this menu is the amount of time in minutes detected motion will temporar ily pl...

Page 17: ...ing the pointed object into the socket from the back side can be helpful When installing the cover it may be helpful to ap ply more pressure toward the bottom of the cover Replace the backplate NOTE W...

Page 18: ...al power up or restart the motion occupancy sensor requires about 30 seconds before it will begin responding to motion The motion occupancy sensor initiates override only during off times in the sched...

Page 19: ...e 5 Check baud rate see Advanced Communications BACnet on page 10 Reduce the Max Master number down to the minimum needed for that network see Advanced Communications BACnet on page 10 See Wiring Issu...

Page 20: ...No voltage may indicate a bad connection or simply no active network NOTE Wiring must be adequate to avoid excessive voltage drop on long runs Allow plenty of cushion in measurements A meter may be t...

Page 21: ...urns all object values to their relinquished defaults until they are updated by the MAR7000 s programs restarts the controller s Control Basic programs and leaves configuration and programming intact...

Page 22: ...ion and Basic Operation 7 Home Main Menu and Override Screens 7 Navigation 7 Room Temp Setpoint Adjustment 7 Main Menu and Settings 7 H C Fan Occupancy and Override 7 Configuration General 8 Advanced...

Reviews: