19
2.10 Power Cable
Please follow the local wiring regulations. Follow environmental conditions and
refer to IEC60950-1.
2.10.1 AC input and output maximum current and power cable configuration.
Model
20KVA
40KVA
60KVA
Current (A)
36.8
73.6
110.4
Power cable (mm
2
)
6
16
35
Fixation torque force (lb-in)
60
60
60
Model
30KVA
60KVA
90KVA
Current (A)
55
110
165
Power cable (mm
2
)
10
35
70
Fixation torque force (lb-in)
60
60
60
Note: Installer has to consider the max. current and wiring gauge when considering future
extension.
2.10.2 DC input maximum current and power cable configuration.
Model
20KVA
40KVA
60KVA
Current (A)
67
134
200
Power cable (mm
2
)
15
50
95
Fixation torque force (lb-in)
60
60
60
Model
30KVA
60KVA
90KVA
Current (A)
100
200
300
Power cable (mm
2
)
25
95
150
Fixation torque force (lb-in)
60
60
60
Warning:
1.
The standard battery cabinet can contain 120 pcs of 12V 9Ah battery. If the load rating is over
60KVA, only one battery cabinet is not sufficient for the discharging current. At least one more
battery cabinet has to be installed in parallel.