54208003-13 

 

 

 

 

CONDENSATE DRAIN DHPU(L)

 

 

The DHPU(L) coil will act as an evaporator during  the 
heating cycle and create water. 

A condensate drain 

must be fitted.

 

Remove  the  plate  from  the  valve  end  mounting  foot 
and fit a 22mm ID hose to the copper stub. 
Route the hose through one of the knockouts. 

 

A  5m  head  condensate  pump  kit  (54300452)  is 
available  for  applications  where  gravity  drain  is  not 
possible. 

 

 

 

 

Each unit is supplied with air inlet and discharge spigots.(see page 2 for sizes) 

 

These may be used for connecting installers ducting or used with the optional duct, plenum and grille kits 
(refer to kit instructions for installation) 

 
 

NOTE: 

It is essential that ducting is adequately insulated to prevent sweating. An insulation thickness of at 

least 45mm is recommended. 

 
 
 
 
 
 
 
 
 

 

 
 

 

To maximise performance, pipe runs should be kept as short as possible. However, individual pipe runs 
to a maximum of 80m (50m on sizes 15 & 20) including 20m lift are permissible, provided good 
refrigeration practice is followed. 

 

Performance rating is based on 7.5m pipe runs. Correctly sized pipes for each installation and fitting the 
correct expansion orifice will result in no significant loss of capacity on extended pipe runs. 

 

Pipe sizes are based on:- 
Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow. 
Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow. 
Maximum of 15.2 m/s (3000 fpm) suction gas. 

Where vertical risers exceed 5m, oil traps must be formed in the pipe. This will help ensure that 
oil returns to the compressor. Typically fit an oil trap every 3m with a trap at the bottom of the 
riser. 

 

 

B

 

CONDENSATE DRAIN DHPU(L) 

 

DUCTWORK 

 

PIPEWORK 

 

Summary of Contents for DCU+ 15

Page 1: ...g parts and refrigerant under pressure Always site out of reach of children and protect from vandalism 3 The units have fan speed control start delay timer HP and LP switches and a contactor fitted as...

Page 2: ...560 1174 490 65 65 240 392 865 404 81 DCU 60 1100 510 560 1174 490 65 65 240 392 865 404 81 DCU 80 1100 510 560 1174 490 65 65 240 392 865 404 84 DHPU L 15 930 510 495 1004 490 65 120 210 317 757 354...

Page 3: ...ers to suit IMPORTANT The stabilizing brackets provided MUST be used when suspending a unit Fit the stabilizing brackets to the top corners of the backpanel and front face using the No 10 screws provi...

Page 4: ...n thickness of at least 45mm is recommended 1 To maximise performance pipe runs should be kept as short as possible However individual pipe runs to a maximum of 80m 50m on sizes 15 20 including 20m li...

Page 5: ...Use the shortest possible route avoiding sharp bends 5 Fully insulate both the suction and expansion lines including the expansion device since both lines may sweat FITTING LOSSES in equivalent strai...

Page 6: ...check valve is needed The expansion assembly and line must be fully insulated Note The indoor units listed below are fitted with heating capillarys WM60H WM80H WM100H CC875 80H CC875 110H CC875 140H H...

Page 7: ...le charge to a sweat line on the evaporator Typical suction pressures on short lines at UK conditions with maximum evaporator and condenser fan speeds i e during commissioning will be 55 60 psig Take...

Page 8: ...t to suit the refrigerant It may be necessary to adjust this to suit site conditions to raise or lower the nominal head pressure a With the system switched off connect a high pressure gauge to the liq...

Page 9: ...hanges per turn of adjusting screw Pressure change 1 4 0 12 5 bar Clockwise 1 2 bar counter clockwise 1 2 bar Pressure change 2 9 2 21 2 bar Clockwise 2 5 bar counter clockwise 2 5 bar Pressure change...

Page 10: ...hed cables ElectromechanicalSystems Systems including an electromechanical indoor unit require a supply to the condensing unit with connecting cables run to the indoor unit Electronic Systems It is re...

Page 11: ...400V 3 50Hz disjoncteur a fournir 400 3 N 50 abgesicherts versorgung 400V 3 50Hz S S 1 3 7 S S Signal Ansteurung 230V 50Hz 1 3 7 S S SIGNAL 1 230V 50Hz 7 POWER TO SUIT SUPPLY FUSE PUISSANCE FOURNIR U...

Page 12: ...characteristics that allow starting of the compressor yet still afford close overcurrent protection under running conditions The ratings shown are for HRC motor rated fuses DUCTED UNITS DCU 15 DCU 20...

Reviews: