3
54208003-13
Ducted units are designed to be hung on a wall (brackets available as a kit), suspended from a ceiling
(installer supplied fittings), or to stand on a flat surface. Whichever method is used it is essential that the
mounting surface is capable of supporting the unit's weight. Leave space around the unit for air circulation
and access for installation and maintenance.
FLOOR MOUNTING
Using the appropriate side of the packing carton as a template, (centres marked A), mark out and drill 4
holes to suit maximum M8 bolts (also see Fig. 1). Secure the unit to the floor. Discard the 4 stabilizing
brackets and 8 screws.
DCU+
DHPU(L)
A
(mm)
B
(mm)
15 to 40
15 to 30
930
510
50 to 80
40 to 60
1100
510
SUSPENSION MOUNTING
The installer must supply 4 x M8 threaded rods with 16 nuts and
washers to suit.
IMPORTANT:
The stabilizing brackets provided
MUST
be used when suspending a unit.
Fit the stabilizing brackets to the top corners of the backpanel and front face using the No.
10 screws provided, (2 per bracket).
If these brackets are omitted the unit will be subject to unacceptable movement on
compressor start (Fig. 2).
Where long drops of M8 rod are used, it is advisable to incorporate flexible pipes in the suction and
expansion lines.
Using the template printed on the side of the packing
carton, (centres marked A), mark out the ceiling and
drill 4 holes to suit M8 screwed rod, (see Fig. 1).
Raise the unit to the required height and pass the
screwed rods through the mounting holes in the units
feet and stabilizing brackets. Secure the unit with a
nut and washer on either side of each stabilizing
bracket and two nuts and washers underneath each
foot mounting hole, (Fig. 2).
FIG.2.
WALL MOUNTING
Wall mounting brackets are available as an optional Kit (53200407)
FIG.1.
OR
MOUNTING