FUSES
The system and its supply/interconnecting wiring must be protected by fuses, preferably High Rupture Current
(HRC) motor rated types (to EN 60269) or miniature circuit breakers (to EN 60898) or local codes having similar
time lag characteristics, that allow starting of the compressor yet still afford close overcurrent protection under
running conditions. The ratings shown are for HRC motor rated fuses.
DUCTED UNITS
DCU+ 15
DCU+ 20, DCU+ 30
DCU+ 40
DCU+50, DCU+ 60
DCU+ 80
DHPU(L)15
DHPU(L)20
DHPU(L)30
DHPU(L)40
DHPU(L)50
DHPU(L)60
1Ph (Amps)
13
16
16
20
25
32
3Ph (Amps/Phase)
---
---
10
10
10
16
NOTE:
REFER TO THE RELEVANT INDOOR UNIT INSTALLATION INSTRUCTION FOR ALL OTHER SYSTEM
FUSE SIZE.