background image

 

 
RECEIVING AND INSPECTION 

 

Upon receiving the product, check to make sure all 
items are accounted for by referencing the Bill of Lading 
to ensure all items were received. Inspect each carton 
for shipping damage before accepting delivery. Notify 
the freight carrier if any damage is noticed. The carrier 
will make notification on the delivery receipt 
acknowledging any damage to the product. All damage 
should be noted on all copies of the Bill of Lading which 
is countersigned by the delivering carrier. A Carrier 
Inspection  Report  should  be  filled out  by  the  carrier 
upon  arrival and  a  report  given  to the Traffic 
Department. If damaged upon arrival, file a claim 
immediately with the carrier. Any physical damage to 
the unit after acceptance is not the responsibility of 
Mars Air Systems. 

 

UNPACKING 

 

Verify that all parts, components and accessories, and 
the correct quantities of each have been received. If any 
items are missing, report shortages to Mars Air 
Systems directly to arrange for obtaining the missing 
items. Again, verify quantities received against those on 
the  Bill of Lading only, as multiple shipments may be 
involved. 

 

INSTALLATION 

 

Typical Mounting  –  Wall  or Ceiling  Mounted 
Horizontally Above the Door Opening 

 

1.  Overhead installation is recommended to prevent 

the possibility of the unit falling if the wall to which 
the unit is mounted is hit by a truck or material 
handling device. If however, wall or bracket 
mounting is preferred, additional holes may be 
drilled in the side panels of the housing. 

 

Note

: Bracket/Support mounting is not generally 

recommended for Air Curtains equipped with steam 
or hot water coils. Overhead installation using 
threaded rods with independent suspension of coils 
is recommended. 

 

2.  Center the unit over the opening. The air curtain 

shall be equal to or greater than the width of the 
opening. 

 

3.  Four pre-punched 1/2” mounting holes on the top of 

the unit are provided for your convenience. These 
holes must be utilized to secure the product 
overhead. All hardware is field provided by others. 

4.  Mount the product such that the discharge is 1” 

above the opening and all obstacles. (FIG. 1) 

Note: 

If the product is installed higher than the 

recommended 1” above the opening, then it must be 
moved 3/8” away from the wall for every 1” that it is 
moved up. Any void between the wall and the product 
must be sealed, by others, to optimize performance. 

 

 

FIG. 1 

 

5.  Use four (4) threaded rods for overhead installation 

or four (4) threaded bolts for wall installation. All 
hardware is field provided by others. (FIG. 1) 

6.  If applicable, for tandem installation or products 

mounted side by side, allow no more than 6” 
between the two products. For overhead installation 
using threaded rods, the products may require a 
beam, by others, to span the full distance of the 
mounting length. (Reference 

Accessory 

Installation Supplement

7.  All wires must be connected to the external junction 

box(s) of the unit. 

8.  The unit must be wired per NEC and local codes. 

 

Electrical Field Wiring  

 

The unit and any optional accessories must be wired 
with the proper voltage to the junction box per the wiring 
diagram. (FIG. 2, unheated products only) 

 

 WARNING 

Precaution should be taken in explosive atmospheres. 

Summary of Contents for WMH Unheated Series

Page 1: ...without notice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA WMH Unheat...

Page 2: ...tice Such revisions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Table of Contents Pa...

Page 3: ......

Page 4: ...see table above for models available CSA Certified to conform to UL 507 US and CSA 22 2 Canada Standards Indoor Outdoor Use Top and wall mounting holes provided 5 8 Cabinet has sufficient strength fo...

Page 5: ......

Page 6: ...nged door type door limit switch installation FIG 1 2 Use light gauge materials when field fabricating brackets to activate and deactivate the door limit switch s FIG 2 Figure 2 also shows the typical...

Page 7: ...6 STD SHOWN 3 Extended Wall Mounting For Tandem Mounting of air curtain over sectional style door use either wall mounting angle brackets or threaded rods 4 Top Mounting Brackets For overhead installa...

Page 8: ...s The WMI WMH Series can be configured with Flat Bank or V Bank Filter Sections as options GENERAL SAFETY INFORMATION Use this product only in the manner intended by the manufacturer If you have any q...

Page 9: ...s of the housing Note Bracket Support mounting is not generally recommended for Air Curtains equipped with steam or hot water coils Overhead installation using threaded rods with independent suspensio...

Page 10: ...blower wheels note direction arrows on the blower wheel housing Correct if needed by changing polarity of three phase power L VERY IMPORTANT Using a clamp meter measure the amperage to each motor and...

Page 11: ...all the product reverse the procedures above 8 Reconnect the power source to the product 9 If you have any questions regarding the maintenance of the product contact the manufacturer SPECIAL APPLICATI...

Page 12: ...bstruction on intake or discharge Remove obstruction or move air curtain Power leads out of polarity Switch power leads to correct polarity 3 phase models only Blower motor rotating below normal speed...

Page 13: ...ema 1 1 115 1 1 6 2 4 03 015 7124 1096 Genteq Nema 1 1 208 230 1 6 5 9 2 03 015 Nidec Nema 1 1 208 230 1 4 3 6 5 03 014 K55BWJZB 2362 US Nema 1 1 115 1 1 2 1 03 015 US Nema 1 1 208 230 1 3 2 6 3 Black...

Page 14: ...ninterrupted or error free operation of Mars product Under no circumstance is Mars liable for any of the following 1 Third party claims against you for damages or 2 Special incidental or indirect dama...

Page 15: ...CLUDES A Air curtains for pedestrian entrances B Air curtains for vehicular entrances C Air curtains for large loading dock doors 1 2 RELATED SECTIONS A Section 05 50 00 Metal Fabrications Concealed s...

Page 16: ...for Forced Circulation Air cooling and Air Heating Coils F CRN Canadian Registration Number Coil G ANSI Z223 NFPA 54 National Fuel Gas Code H NEC National Electric Code 1 4 SUBMITTALS A Submit under...

Page 17: ...on B Installer Qualifications Minimum five years documented experience installing products specified in this Section 1 6 DELIVERY STORAGE AND HANDLING A Store products in manufacturer s unopened packa...

Page 18: ...s indicated d Electrical Characteristics 208 230V AC three phase 19 0 15 8 Amp full load per motor fan e Electrical Characteristics 460V AC three phase 7 9 Amp full load per motor fan f Electrical Cha...

Page 19: ...vanes with a plus minus 40 degree sweep front to back 2 Air Velocity at Nozzle a WMH 96 2 99 Inch 2516 mm Wide Units 3732 feet min 18 9 m s two 5HP motor fan assemblies b WMH 120 2 123 Inch 3126 mm W...

Page 20: ...coils for field mounting on air intake side of the air curtain cabinet with opposite end connections 1 Output Air curtain manufacturer s standard one row coils 2 Output Air curtain manufacturer s stan...

Page 21: ...ch is used to automatically start and stop the air curtain Thermostat is included with optional motor control panel for field installation Provide motor control panel as follows 1 Thermostat Wall moun...

Page 22: ...3 1 EXAMINATION A Verify that required utilities are in correct location and are of correct capacities for specified products B Verify openings to receive air curtains are plumb level square accurate...

Page 23: ...asuring air temperature 6 inches off the floor Optimal reading is halfway between the temperature inside and outside the building 3 4 CLEANING A Clean air curtains promptly after installation in accor...

Page 24: ...ions do not entitle the buyer to corresponding changes improvements additions or replacements for previously purchased equipment MARS AIR SYSTEMS LLC GARDENA CA USA Reference Links Link Description ht...