Installation and Operation Manual  -  

WHDEHUM-90P

5

splashed and that it is wired into a GROUND 

FAULT INTERRUPTER protected circuit.

5. 

A secondary drain pan MUST be placed under 

the unit if installed above a living area or above 

an area where water leakage could cause dam-

age (see local codes for other requirements)

6. 

DO NOT position the dehumidifier directly on 

structural members where noise or vibration 

may be objectionable. The unit is equipped with 

adjustable support feet to raise and level the 

unit from the mounting surface; these adjust-

able feet should be utilized to provide improved 

drainage from the drain pan and should be 

adjusted to tilt slightly toward the drain utilized.

7.  The unit should be located near the existing 

air handling system to minimize the required 

ductwork for connection of the dehumidifier to 

the existing HVAC air handling system. When 

the option is used, the control (humidistat) unit 

must be located in the space that is to be con-

ditioned. The control (humidistat) 

must

 be low 

voltage (24V) and should be connected to the 

unit with code approved, low voltage thermostat 

cable.

8. 

When locating the dehumidifier in areas of ex-

treme heat or high humidity, >120-degrees/90% 

humidity, additional external insulation may be 

required to prevent undesired condensation on 

the exterior of the unit. 

Common Installation Instructions Across All 

Configurations

Step 1: Placement of the Dehumidifier Unit

IMPORTANT: If the dehumidifier unit is handled in 

such a manner that the compressor did not remain 

in the upright position, it is necessary to place on 

a level surface and wait a minimum of two hours 

before turning the unit on.

Additionally, the Comfort-Aire/Century dehumidifier 

cannot sit directly on the floor unless the unit 

condensate drain output is feeding directly into a 

sump pump next to it.

When placing, the dehumidifier unit is equipped 

with adjustable feet that can be used along with a 

leveling tool to make sure the dehumidifier rests in 

a completely “level” final state as needed for proper 

operation.

Step 2: Set Up Drain Line

The condensate drain line should be routed to a 

suitable drain to carry the condensate water to the 

outside.  The drain line must flow down without any 

loops, dips, or valleys to the final drain hole.

Recommended Dehumidifier Drain Config-

uration Including a Transition to PVC Pipe

1. 

Cut a piece of ¾” OD PVC that is 6” minimum.

2. 

Insert PVC into a ¾” elbow, then attach a ¾” 

OD length of PVC to drain.  Keep the length 

of the PVC drain pipe to a minimum and make 

sure it flows down.

3. 

Insert the open end of the dehumidifier 

condensate tubing into the ¾” pipe so that 

it does not extend into the elbow fitting.  For 

proper flow, a minimum downward slope of 

1” per 10’ run is required.  NOTE: If a proper 

downward angle is not possible, then it is 

recommended to use an external condensate 

Installation

WARNING

Standalone Unit Dehumidification configu-

rations, as noted, are typically used to dry 

basements and crawlspaces.  To be properly 

dehumidified, the area to be controlled should 

be sealed with a vapor barrier.  If the unit is to 

be installed in a crawlspace, all vents to the 

outdoors should be sealed.  Do not install your 

humidifier in a corrosive environment.  Some 

liquid barriers dry via “solvent evaporation”.  

Always ensure the barrier is completely dry and 

area is thoroughly ventilated before installing 

dehumidifier.

Figure 3. 

Drain Tube Drawing

Summary of Contents for Comfort-Aire Century WHDEHUM-90P

Page 1: ...www marsdelivers com Installation and Operation Manual WHDEHUM 90P Whole House Dehumidifier...

Page 2: ...trary to these guidelines may void warranty The benefits of a properly humidified environment are many They include personal comfort as well as the preservation of furniture draperies carpets wooden f...

Page 3: ...t operating in standalone unit mode Condensate pump if not easy to reach gravity fed drain Air duct take offs and conversions as necessary if not operating in standalone mode ID plastic or vinyl drain...

Page 4: ...uire dehumidification As of late there is a growing trend towards mini split HVAC systems that are implemented as heating and cooling systems Separated dehumidification configurations are ideal soluti...

Page 5: ...wait a minimum of two hours before turning the unit on Additionally the Comfort Aire Century dehumidifier cannot sit directly on the floor unless the unit condensate drain output is feeding directly i...

Page 6: ...en installing the dehumidifier inside a sealed crawlspace a basement or a sealed attic the ducting requirements are recommended as follows 1 If the area is open without partitions and the dehumidifier...

Page 7: ...d or unconditioned area An example would be to feed the separate room from the main living area which would maximize the airflow from there proving a living area that likely is more dry than the other...

Page 8: ...OSESTO DISABLE DEHUMIDIFIER G If the dehumidifier is installed in an attic leak protection the unit should be place a normally closed condensate overflow s Wire the float switch to terminals A5 and R...

Page 9: ...reen The display screen has two functions When the unit is powered ON it shows the local humidity While setting the desired humidity level the screen will show the set point humidity level 2 Power Ind...

Page 10: ...iated float switch is open Step 2 Push the power switch to turn the dehumidifier ON Step 3 Press the Central Control button until the Whole House light turns on which indicates the unit is configured...

Page 11: ...delivers com within 60 days of purchase The original consumer must retain a receipted bill of sale as proof of warranty period part numbers serial numbers purchase and installation dates REMEDY PROVID...

Page 12: ...GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEO...

Reviews: