7
PLUG
P11-P12
GASKET
COVER PLATE
P13-P14-P15
TRASH SCREEN
Figure 1A and 1B. The bottom outlet arrangement is also used for
equalizer connections between basins.
The typical attachment of customer piping for bottom outlet or equalizer
with flange connection using gasket (supplied by Marley) is shown in
Figure1. Sealing washers (by others) required at bolt connections
inside basin. The tower is not designed to support additional piping
loads. Do not support piping from the tower.
Installation
Figure 1
Install plug in side-outlet location for models P11 and P12. Remove
side-outlet connection assembly on larger models and install cover
plate using sealer as shown in Figure 1.
4.
The welded galvanized pipe assembly utilized on some models P14
and P15 ships within the tower basin. Unbolt as shown in Figure 1A
and reinstall as shown in Figure 1B. Apply sealer as shown and reuse
existing hardware as well as additonal hardware shipped with tower.
If a weld connection is used, it is recommended that the weld area be
protected against corrosion. Cold galvanizing is suggested, applied
according to the manufacturer’s instructions.
➠