5.10 Change language
Language options: NL, EN, DE, FR, PL, RO, LT.
5.11 Calibration temperature
If the external room sensor is installed in an unfavourable position, the actual temperature and the
temperature measured by the PinTherm Connect may differ. This temperature difference can be
compensated by setting a correction factor in this temperature calibration function.
For example:
The measured temperature is 18°C, but the PinTherm Connect display
indicates 20°C. The difference in this example is 2°C too high.
The correction value must be set to -2°C.
5.12 Heating/Cooling
Setting to make the controller suitable for controlling heating or cooling.
HEATING/COOLING
HEATING
back to
the menu
select
change setting
OK
HEATING/COOLING
OK
ENGLISH
SELECT LANGUAGE
back to the
menu
select the desired
language
select
OK
OK
CHANGE LANGUAGE
CALIB. TEMP.
CALIB. TEMP.
Correctionvalue is adjustable
back to the
menu
select
changes the
flashing digit
to go one digit up
OK
OK
+ 0.0°C
from -3,5°C to +3,5°C