background image

 

  SP9 ServiceManual.docx 06/02/2015 

 

 

Page 8 of 42 

 
Operating  SP9 Undercounte r  Unit for the  Firs t T ime: 

  Check that all installation procedures have been carried out. 

  Ensure water is connected to unit, valve is turned on and power cord is connected and 

plugged in to wall socket. 

 

The “power on” light will glow green and the machine will fill to a safe level, above the 
elements, before heating.  The display will show the current water temperature and the 
status “Filling…” 

 

The “Ready/Status” light will cycle two red flashes while the machine is filling to the safe 
level.  

  After this amount of water has heated to about 94ºC, the boiler will draw more water in until 

the temperature drops by 1 or 2 degrees.  The boiler will then heat again.  This heat fill cycle 
continues until the boiler is full. 

  Ensure the Undercounter unit is set to SP9 mode for use with the SP9 brewer. See Menu 

Navigation section in this manual 

  While 

filling, the “Ready/Status” light will remain blank. 

 

The “Ready/Status” light will glow green when the machine is both full and up to normal 
operating temperature. Allow approximately 15 minutes. 

  The boiler is now ready for use 

– the display will show the Water Temperature and the 

status “READY”. 

 

5. SETUP AND CALIBRATION: 

 

Operating the Head Unit for the first time: 

To help prevent heat loss between the Undercounter unit and the Head unit the silicone hose can 
be insulated with hose insulation. Simply cut the insulation to the correct length required. 
Once the Head Unit installation procedure has been carried out, place a 1 litre jug under the 
dispense head. Set the dispense volume to 750ml and press the start switch twice. This will 
dispense 750ml in one delivery, without pausing. Measure the dispensed volume to confirm factory 
calibration (750ml 

+

 10ml). If the volume is not satisfactory, proceed to the calibration procedure 

below to calibrate the Head Unit. The calibration should only be conducted by a trained service 
engineer. See guidelines below. 
 

Dispense Volume Calibration 

1. Once all installation procedures are carried out the Head Unit is ready to be calibrated. 
2. Turn volume dial to Max. Set Brew Time to 2 minutes. 
3. Place large container (>1 litre) of known weight under spray head. 
4. Initiate brew. 
5. Weigh & record brew output. 
6. The output should be 750g, plus or minus 10g. 
7. If output is within 10g of 750g calibration is complete. 
8. If not, enter calibration mode by holding down toggle switch for min 3 sec. 
9. A long beep will sound to confirm the unit is in calibration mode. 
10. Enter the volume recorded via the brew switch using the following example: 

  If 724g was measured 

  The toggle switch is used to input each digit successively 

Summary of Contents for 1000830

Page 1: ...tem Twin Single 1000830 1000831 1000832 1000833 SERVICE MANUAL Marco Beverage Systems Ltd 63d Heather Road Sandyford Industrial Estate Dublin 18 Republic of Ireland Ireland Tel 01 295 2674 Ireland Fax...

Page 2: ...peration 10 7 Menu Navigation 13 8 User Setup Options 14 9 Service Setup Options 15 10 Diagnostics 17 11 Display Status Messages 18 12 Routine Maintenance 19 13 Component Access Under Counter Unit 22...

Page 3: ...f fire electric shock burns or other injuries or damages Read all operating and safety instructions carefully This machine must be earthed If the moulded plug supplied is not used then ensure that the...

Page 4: ...tment or similar functional departments 3 SPECIFICATIONS Table 1 SP9 Boiler 4L 2 4kW Dimensions Height mm Width mm Depth mm 565 155 395 Performance Immediate Draw Off litres Max Hourly Output L hr 4L...

Page 5: ...valve of the boiler 3 4 BSP Make sure the sealing washer is fitted here also Turn on water and check for leaks Installation of SP9 Head Unit A full A4 sheet sized version of the counter cut out templ...

Page 6: ...ce between head and boiler refers to the length of the tubing Since the tubing is never a straight line actual distance between head and boiler can be substantially less than 400mm depending on alignm...

Page 7: ...SP9 ServiceManual docx 06 02 2015 Page 7 of 42 Figure 3 Figure 4...

Page 8: ...erating the Head Unit for the first time To help prevent heat loss between the Undercounter unit and the Head unit the silicone hose can be insulated with hose insulation Simply cut the insulation to...

Page 9: ...toggle the toggle switch 2 times A long beep will sound To enter the 4 toggle the toggle switch 4 times To enter a 0 value simply do not toggle the toggle switch If calibration is successful a long be...

Page 10: ...it SP9 can also be configured as a Single System with a single head unit operating with a single under counter unit In brew mode once the brew switch is toggled SP9 will recirculate hot water for 15 s...

Page 11: ...SP9 ServiceManual docx 06 02 2015 Page 11 of 42 CONTROLS Figure 6 BREWING...

Page 12: ...brew time also referred to as the dispense or contact time using the lower control knob Start the brew by pressing the toggle switch once Three beeps will be heard when the brew cycle has completed F...

Page 13: ...unter unit is set to SP9 Mode for use with the SP9 head unit The SP9 Undercounter Unit has many settable features which gives the operator greater flexibility in choosing how the unit will operate Mai...

Page 14: ...an set the temperature of the tank Use the navigation instructions above to change the temperature NOTE Temperature should never be set for more than 96 C as it may cause steam to be generated during...

Page 15: ...and element power This is a factory setting and should only be changed by trained personnel Range 0 20 0 seconds Resolution 0 1 second 3 0 No 4 Sets the time at which machine waits for the water too c...

Page 16: ...it Celsius No 9 This sets max limit of the temperature that user can set in USER SETUP max value is 98 5 degrees Celsius 98 5 No 10 Press the eco button to save all the values and reboot the machine T...

Page 17: ...of 42 Table 4 11 DISPLAY STATUS MESSAGES Status Description BOILER OFF Machine off Display backlight off but temperature read out still working FILLING Water level below low level probe Machine is fil...

Page 18: ...cooling process DESCALE TANK Descale timer elapsed Time to descale the tank CHANGE FILTER Litres output exceeds set value Time to change the water filter CHECK LOW PROBE Low water level probe broken d...

Page 19: ...o damage any attachments Use ScaleKleen Marco part No 8000270 or similar Follow instructions carefully Thoroughly clean and flush the machine before re use Clean water level probes with ScotchBrite Fo...

Page 20: ...SP9 ServiceManual docx 06 02 2015 Page 20 of 42...

Page 21: ...SP9 ServiceManual docx 06 02 2015 Page 21 of 42...

Page 22: ...9 Head to the under counter unit the electrical connection should be connected to DIN1 the water feed to the Head Unit should be connected to A1 and the water return from the Head Unit should be conne...

Page 23: ...op lid and the top tank insulation inside Figure 10 Water Tank Lid Removal Remove the four 10mm hex nuts retaining the tank lid to gain access to the interior of the water tank There s no need to remo...

Page 24: ...SP9 ServiceManual docx 06 02 2015 Page 24 of 42 Internal Component Map Figure 13...

Page 25: ...Mains Live In Tab 6 Relays Heater 7 Heater Tab 8 On Off 2 way Connector Link Inserted 9 LED 5 way Connector 10 Earth Tab 11 Daughter PCB Connector low voltage 12 External Connector 13 Thermistor Conne...

Page 26: ...ure 15 Before fitting the replacement main control board ensure the DIP switch settings correspond to those of the original control board as noted earlier Ensure all connections have been replaced in...

Page 27: ...cket by two screws accessible from the bottom of the bracket Remove the two screws and the cable connections if applicable and remove the 24vdc power supply Replace the 24vdc power supply and the cabl...

Page 28: ...on next page Note Do not over tighten the retaining nuts as this could deform the seals and cause leakage Over Temperature Cut Out Replacement To replace the over temperature cut out switch remove the...

Page 29: ...ee main panels as indicated in the diagram below Top Flat Panel Remove 3 screws Before removing top flat panel remove the reservoir gasket No 9 on Spare Parts Schematic Front Flat Panel Remove 4 screw...

Page 30: ...de the head unit Replace the control board by following the preceding instructions in reverse Reservoir and Solenoid Replacement Remove the front curved panel as described previously Disconnect the wi...

Page 31: ...SP9 ServiceManual docx 06 02 2015 Page 31 of 42 15 ELECTRICAL SCHEMATICS...

Page 32: ...SP9 ServiceManual docx 06 02 2015 Page 32 of 42...

Page 33: ...SP9 ServiceManual docx 06 02 2015 Page 33 of 42 16 SPARE PARTS SCHEMATICS...

Page 34: ...SP9 ServiceManual docx 06 02 2015 Page 34 of 42 SP9 Under Counter Unit Spare Parts Part 1 SP9 Under Counter Unit Spare Parts Part 2...

Page 35: ...SP9 ServiceManual docx 06 02 2015 Page 35 of 42...

Page 36: ...SP9 ServiceManual docx 06 02 2015 Page 36 of 42...

Page 37: ...SP9 ServiceManual docx 06 02 2015 Page 37 of 42 SP9 Head Unit Spare Parts...

Page 38: ...B Splurty Dials 1 1800735 Knob dial 2 1501932 Switch Toggle Mom 1 1402160 Tailpiece Hose 1 4 BSP X 12mm 6 SP9 Under Counter Unit P N 1000831 Spare Parts Part Description Qty 1501559A Pump Topsflo 24V...

Page 39: ...SP9 ServiceManual docx 06 02 2015 Page 39 of 42 18 DIMENSIONED DRAWINGS...

Page 40: ...SP9 ServiceManual docx 06 02 2015 Page 40 of 42...

Page 41: ...SP9 ServiceManual docx 06 02 2015 Page 41 of 42 19 CUT OUT TEMPLATE...

Page 42: ...SP9 ServiceManual docx 06 02 2015 Page 42 of 42 Installation Cut Out Template...

Reviews: