24
UP and DOWN Contact Inputs
Remote set point adjustment may be accomplished
by connecting a SPDT momentary contact switch
to the J1 connector UP and DOWN contacts. To
connect this switch, the common terminal must be
connected to J1-4 (CGND). The other two switch ter
-
minals are connected to J1-2 (UP) and J1-3 (DOWN).
Refer to
Section 4 – Features and Protection
for a
detailed description of the UP and DOWN contact
function.
Parallel Generator Compensation Enable/Disable
(DROOP OFF)
A user can enable or disable the integrated load
sharing function of the regulator by opening or
closing contact between J1-10 (DROOP OFF) and
J1-4 (CGND). Closing the contact disables the droop
function. Refer to
Section 4 – Features and Protection
for a detailed description of the Load Sharing
function.
Excitation Enable/Disable (EXCITATION OFF)
A user can enable or disable excitation by opening
or closing contact between J1-11 (EXCITATION OFF)
and J1-4 (CGND). Closing the contact disables exci
-
tation. Refer to
Section 4 – Features and Protection
for a detailed description of the Excitation Off
function.
Auxiliary Input (AUX_IN (+), AUX_IN (-), and AUX_
LOOP)
This input allows a user to control the regulator with
an auxiliary piece of equipment by connecting a
voltage source to J1-1 (AUX IN +) and J1-12 (AUX IN
-). The regulator can also be configured to accept a
voltage or current to be metered on this input. Refer
to
Section 4 – Features and Protection
for a detailed
description of the Auxiliary input function.
VAR/PF Enable/Disable (VAR/PF_OFF) (EC+ only)
A user can enable or disable the VAR or PF regula-
tion modes by opening or closing contact between
J1-9 (VAR/PF_ON) and J1-4 (CGND). Opening the
contact enables VAR/PF regulation if the regula
-
tion mode was set to VAR or PF in the HMI or
DVRPortal™. Refer to
Section 4 – Features and
Protection
for a detailed description of the VAR/PF
regulation function.
Note: Operation in VAR or PF modes should only
be enabled when the generator is paralleled with
utility (infinite bus). If the VAR/PF_OFF is open
during power up of the regulator in VAR or PF reg-
ulation modes, a Generator Start Up Fault occurs.
5
Installation
Pin Number
Name
Description
1
AUX IN (+)
Auxiliary input positive
2
UP
UP contact input (active low)
3
DOWN
DOWN contact input (active low)
4
CGND
Input common
5
AUX_LOOP
Auxiliary current loop jumper
6
CONTACT1
Contact output
7
CONTACT2
Contact output
8
AUX_LOOP
Auxiliary current loop jumper
9
VAR/PF_OFF
VAR/PF regulation disable contact (active low, EC+ only)
10
DROOP_OFF
Droop disable contact input (active low)
11
EXCITATION_OFF
Excitation disable contact input (active low)
12
AUX IN (-)
Auxiliary input negative
Table 5-3. Connector J1 System Connections
GPN046 04-13.indd 24
4/5/13 10:24 AM
Summary of Contents for DVR 2000E+
Page 1: ...DVR 2000E EC User Manual A Regal Brand...
Page 21: ...19 5 Installation Figure 5 2 DVR Rear dimensions with cover Valid for E EC versions...
Page 22: ...20 5 Installation Figure 5 3 Cutout and Drilling Dimensions...
Page 57: ...55 8 Maintenance and Troubleshooting...
Page 58: ...56 8 Maintenance and Troubleshooting...
Page 60: ...58 8 Maintenance and Troubleshooting...
Page 61: ...59 8 Maintenance and Troubleshooting...
Page 62: ...60 8 Maintenance and Troubleshooting...
Page 69: ...67 Notes...
Page 70: ...68 Notes...
Page 71: ......