22
5
Installation
Figure 5-4. DVR
®
Rear Panel Connectors
Quick Connect Terminals
Application Notes
No.
Description
CT2
Phase B CT (X2)
For connection of (1) user supplied current transformer with 5A secondary
current. H1 must face generator. Observe polarity.
CT1
Phase B CT (X1)
F+
Exciter Field (+)
Excitation output. Never apply a voltage to these terminals. Observe
polarity.
F-
Exciter Field (-)
E3
Sensing Voltage 3
Phase C for 3 phase output. Jumper to E2 for single phase.
E2
Sensing Voltage 2
Phase B for 3 phase output. L2 input for single phase.
E1
Sensing Voltage 1
Phase A for 3 phase output. L1 input for single phase.
3
PMG Input 1
Protected by regulator fuse. 180-240Vac, 250-300Hz, 350VA
4
PMG Input 2
Do not ground or apply direct current to Terminals 3 or 4.
GND Chassis Ground
Use #12 AWG (4 sqmm) minimum conductor.
Table 5-1. Quick Connect Terminals
GPN046 04-13.indd 22
4/5/13 10:24 AM
Summary of Contents for DVR 2000E+
Page 1: ...DVR 2000E EC User Manual A Regal Brand...
Page 21: ...19 5 Installation Figure 5 2 DVR Rear dimensions with cover Valid for E EC versions...
Page 22: ...20 5 Installation Figure 5 3 Cutout and Drilling Dimensions...
Page 57: ...55 8 Maintenance and Troubleshooting...
Page 58: ...56 8 Maintenance and Troubleshooting...
Page 60: ...58 8 Maintenance and Troubleshooting...
Page 61: ...59 8 Maintenance and Troubleshooting...
Page 62: ...60 8 Maintenance and Troubleshooting...
Page 69: ...67 Notes...
Page 70: ...68 Notes...
Page 71: ......