HMI5000L Installation Guide                                                                                                7

1010-1018 Rev 12                                                                          www.maplesystems.com

Control Panel Grounding

The control panel must be connected to a good, high-integrity earth 
ground both for safety considerations and shielding purposes. Maple 
Systems cannot overemphasize the importance of good grounding. 
Failure to use good grounding procedures during installation may cause 
sporadic malfunction of the HMI.

Connect the HMI chassis ground terminal to a reliable earth ground with 
a low-resistance path. Refer to Figure 1:

  Route all earth ground wires that lead from the HMI, the PLC, the 

power supply, and the line filter to a central earth ground point such as a 
barrier strip. This will ensure that no ground current from one device 
influences the operation of the other devices.

  Connect the HMI chassis ground terminal to the control panel using a 

heavy-gauge short braided cable (#14 AWG) or ground wire to minimize 
resistance. Then, make sure the panel is properly grounded to a clean 
earth ground.

Note:

 If the control panel is made of a non-conductive material, it is 

essential that the chassis ground terminal of the HMI is connected to 
a clean earth ground point located close to the panel. 

  Connect the power cable’s shield wire to the HMI’s chassis ground 

terminal.

  Connect the control panel to earth ground using a copper grounding 

rod close to the HMI and control panel.

  Hinged doors on control panels do not provide a long-term electrical 

connection to the rest of the enclosure. Corrosion develops over time 
and prevents good electrical contact. For this reason, a separate wire 
braid should be installed from the hinged control panel to the rest of the 
enclosure.
For a more in-depth overview of ground wiring techniques, refer to 
Technical Note #1027, “OIT Ground Wiring and Electrical Noise Reduction”  
in the Technical Notes section of the Maple Systems website.

Installation

It is necessary to follow all installation procedures described in this 
chapter for electrical noise immunity and CE compliance. The Maple 
Systems HMI is designed to connect easily to a PLC. External rear 
connectors provide quick connections for power, communications and 
programming wiring.

Summary of Contents for HMI5000L Series

Page 1: ...touchscreens are configured using the EasyBuilder Pro Software For information on programming and configuring the HMI please refer to the EasyBuilder Pro Programming Manual available for free downloa...

Page 2: ...l material in the container against the packing list Maple Systems will not accept responsibility for shortages against the packing list unless notified within 30 days The equipment and accessories we...

Page 3: ...liance The HMIs have been tested to conform to European CE requirements which meet or exceed the noise emissions and immunity requirements as set forth in the EN55022 Emissions and EN55024 Immunity st...

Page 4: ...tional electrical standards when installing the HMI Failure to comply with these restrictions could result in loss of life serious personal injury or equipment damage Warning Do not connect the HMI to...

Page 5: ...wer Supply Selection The power supply used to power the HMI should provide an output of at least 24 VDC 20 measured at the HMI power connector HMI5043DL should be powered with 10 5 28VDC only A DC reg...

Page 6: ...und strap Quiet ground isolated AC Power Line Filter HMI Power Supply Shielded power cable Control panel is tied to a reliable earth ground 2 1 3 4 5 rear side HMI5100L 1 rear side HMI5070L 2 2 3 1 Al...

Page 7: ...round Note If the control panel is made of a non conductive material it is essential that the chassis ground terminal of the HMI is connected to a clean earth ground point located close to the panel C...

Page 8: ...the power cable from the HMI to the power supply The power cable should not be any longer than necessary 2 Install the cable wires referencing the chart below with colors shown for Maple Systems Cable...

Page 9: ...es pits and other features that prevent the gasket from sealing properly If the panel or mounting surface is not uniform thick flat stiff or smooth enough then a sealant such as silicone may be requir...

Page 10: ...cluded with the EasyBuilder Pro software must be installed when downloading from the PC to the HMI via USB connection Caution When connecting two powered devices via USB a difference in potential can...

Page 11: ...arrow icon located in the lower right corner of the screen 3 Click the gear icon to enter the system settings menu 4 When prompted enter the system password default 111111 5 Navigate to the Network ta...

Page 12: ...EN Hide System Toolbar OPEN OPEN SHORT OPEN Boot Loader mode OPEN OPEN OPEN SHORT Reserved OPEN OPEN OPEN OPEN Normal operation Note Place a jumper cap between the respective header pins to set the ju...

Page 13: ...up remove power An internal fuse except 4 3 display models will prevent damage if the polarity of the DC power is incorrect Check wiring to ensure proper connections and try to power up again USB Sti...

Page 14: ...2 wire 1 RX DATA 2 RX DATA 3 TX 4 TX 5 GND 6 TXD 7 DATA 8 DATA 9 RXD Pin COM1 232 RS 1 2 RXD 3 TXD 4 5 GND 6 7 RTS 8 CTS 9 HMI XL 5150 DE9S DE9P HMI5100L HMI HMI LB 5070L 5070 HMI XL 5121 Pin COM1 48...

Page 15: ...485 4W RS COM2 COM3 485 2W RS RS 485 4W COM3 1 DATA RX 2 DATA RX 3 TX 4 TX 5 GND 6 DATA RX 7 DATA TX 8 DATA TX 9 DATA RX Pin COM1 RS 232 232 RS COM3 1 2 RXD 3 TXD 4 5 GND 6 7 RTS TXD 8 CTS RXD 9 GND P...

Page 16: ...Enter the desired IP address or select Obtain an IP Address Automatically to enable DHCP 4 Navigate to the LAN2 tab 5 Enter the desired IP address or select Obtain an IP Address Automatically to enab...

Page 17: ...n addition to the standard RJ45 Ethernet port Supported Wi Fi modes are IEEE 802 11 b g n with WPA PSK WPA2 PSK encryption Wi Fi is off by default To enable and configure Wi Fi 1 Enter the System Sett...

Page 18: ...10 Tap Close to exit the Wi Fi setting window 11 Click Apply to save the changes and OK to exit the system settings menu 12 The updated IP addressing will appear in the Wi Fi tabs of the System Inform...

Page 19: ......

Page 20: ...12 www maplesystems com 2019 Maple Systems Inc All rights reserved Maple Systems Inc 808 134th Street SW Suite 120 Everett WA 98204 7333 Phone 425 745 3229 Email support maplesystems com Web www mapl...

Reviews: