Refrigeration System
INSTALLATION/VISUAL INSPECTION
CHECKLIST
Possible Problem
Corrective Action
Ice machine is not level
Level the ice machine
Improper clearance
around top, sides and/or
back of ice machine
Reinstall according to
the Installation Manual
Ice machine is not on an
independent electrical
circuit
Reinstall according to
the Installation Manual
Water filtration is
plugged (if used)
Install a new water filter
Water drains are not run
separately and/or are
not vented
Run and vent drains
according to the
Installation Manual
WATER SYSTEM CHECKLIST
A water-related problem often causes the same
symptoms as a refrigeration system component
malfunction.
Example: A water dump valve leaking during the
freeze cycle, a system low on charge, and a starving
TXV have similar symptoms.
Water system problems must be identified and
eliminated prior to replacing refrigeration
components.
Possible Problem
Corrective Action
Water area (evaporator)
is dirty
Clean as needed
Water inlet pressure not
between 20 and 80 psi
Install a water
regulator valve or
increase the water
pressure
Incoming water
temperature is not
between 35
°
F (1.7
°
C) and
90
°
F (32.2
°
C).
If too hot, check the
hot water line check
valves in other store
equipment
Water filtration is plugged
(if used)
Install a new water
filter
Water dump valve
leaking during the freeze
cycle
Clean/replace dump
valve as needed
Vent tube is not installed
on water outlet drain
See Installation
Instructions
Hoses, fittings, etc., are
leaking water
Repair/replace as
needed
Water fill valve is stuck
open
Clean/replace as
needed
Water is spraying out of
the sump trough area
Stop the water spray
Uneven water flow across
the evaporator
Clean the ice
machine
Water is freezing behind
the evaporator
Correct the water
flow
Plastic extrusions and
gaskets are not secured
to the evaporator
Remount/replace as
needed
Water does not flow over
the evaporator (not
trickle) immediately after
the prechill
Clean/replace water
level probe as
needed