7
Electrical System
Harvest Sequence
(cont.)
6. HARVEST
The hot gas valve(s) remains open,
allowing refrigerant gas to warm the
evaporator. This causes the cubes to
slide, as a sheet, off the evaporator and
into the storage bin.
*OVERLOAD
FAN CYCLE CONTROL
BIN SWITCH
TB35
TB33
(52)
(51)
(48)
CONTACTOR
CONTACTS
L1
(42)
(66)
(64)
ICE THICKNESS PROBE
WATER LEVEL PROBE
NOT USED
TB35
HIGH PRES
CUTOUT
TB32
L1
(55)
SV1646-6
RUN CAPACITOR
RUN CAPACITOR**
C
S
R
TB34
(53)
(47)
(85)
(86)
COMPRESSOR
FAN MOTOR
(AIR COOLED ONLY)
R
R
(45)
(46)
(50)
PTCR
BIN SWITCH LIGHT
HARVEST LIGHT/
SAFETY LIMIT CODE LIGHT
CLEAN LIGHT
WATER LEVEL
(49)
(63)
(62)
(66)
(65)
(69)
ICE
OFF
CLEAN
(67)
(68)
1F
1C
LOW D.C.
VOLTAGE
PLUG
(62)
1G
TOGGLE SWITCH
68
67
69
66
62
VIEW FOR WIRING
INTERNAL WORKING
VIEW
TB37
(74)
(59)
(73)
(56)
CONTACTOR
COIL
TERMINATES AT
PIN CONNECTION
TB30
TB30
TB30
TB30
L2 (N)
SEE SERIAL PLATE FOR VOLTAGE
(58)
FUSE (7A)
TRANS.
2
4
1
3
5
(61)
(60)
TB31
(76)
(98)
(57)
(99)
(75)
HOT GAS
SOLENOID
DUMP
SOLENOID
(81)
WATER
PUMP
(77)
(80)
(21)
(22)
WATER
VALVE
TB30
TB30
The sliding sheet of cubes swings the
water curtain out, opening the bin
switch. This momentary opening and
closing of the bin switch terminates
the Harvest Cycle and returns the ice
machine to the Freeze Cycle (steps 3-
4).
Self-Contained Models
6. Harvest (Until Bin Switch Activation)
Toggle Switch
ICE
Bin Switch
Closed
Control Board Relays
#1
Water Pump
Open / OFF
#2
Water Fill Valve
Open / OFF
#3
Hot Gas Solenoid
Closed / ON
#4
Water Dump Valve
Open / OFF
#5
Contactor Coil
Closed / ON
Compressor
ON
Safety Controls (Which could stop ice machine operation)
High Pressure Cut-Out
Closed
Main Fuse (On Control Board)
Closed
Summary of Contents for Marine Q 1000