Document Number: 000013527 Rev02  04/19

Subject: K00459 S Model Bin Thermostat 

3. Check for proper operation.

Important

Perform Steps 1 and 2 before performing these steps:

A.

Disconnect the load from the output relay
terminals.

B.

Reconnect the sensor leads and supply power to
the control.

C.

Replace the cover.

D.

Check the control settings for proper values.

E.

Press and hold MENU until SP appears.

F.

Press up and down (arrows) to change the set
point temperature above and below the sensor
temperature until the relay energizes and de- 
energizes.

G.

If the output relay does not perform as indicated,
replace the control.

H.

If proper operation of the control is verified,
reconnect the load.

Summary of Contents for FS9000

Page 1: ...00 or FS9100 FS9000 Assembly and Mounting 1 Move the ice machine and dispenser away from the wall for easier access 2 Bracket selection A Dual evaporator ice machines Use bracket with the shorter top flange B Single evaporator ice machines Use bracket with the longer top flange 3 Remove all panels and control box cover from the ice machine 4 If an ice machine is already installed on the dispenser ...

Page 2: ...nge before re fastening close gap FS9000 FS9100 Continued 7 Route thermistor wire out towards the back of the dispenser Remove unused 7 8 diameter knockout on the back panel snap fit the bushing over the exposed panel hole and route wire into the ice machine control board compartment Internally the cable must be routed as to avoid contact with high voltage high heat or sharp objects 8 Normally the...

Page 3: ... switch wire B Connect the white male bin switch wire to the white female wire of the controller KoolAire Models A Cut the red bin switch wire 3 inches from molex connector on bin switch B Strip wires and install male and female crimp connectors supplied in kit C Connect male and female connectors from the bin thermostat into the newly installed terminals 12 Restore all power to the ice machine an...

Page 4: ...e display then returns to the sensor temperature CHECK PROCEDURE If the control system does not function properly verify that the control is wired and set up properly If the problem persists use the following procedures to determine the cause of the problem nWarning Line voltage is present inside the control Contact with line voltage can cause injury or death Follow these troubleshooting procedure...

Page 5: ... the sensor leads and supply power to the control C Replace the cover D Check the control settings for proper values E Press and hold MENU until SP appears F Press up and down arrows to change the set point temperature above and below the sensor temperature until the relay energizes and de energizes G If the output relay does not perform as indicated replace the control H If proper operation of th...

Reviews: