2.1.3 Australian
Requirements
To be installed in accordance with AS 5601 and AS/NZS 3000:2007 local authorities, gas,
electricity, and any other relevant statutory regulations.
If casters are fitted, the installation must comply with AS5601 and AS1869 requirements.
2.2 Power
Requirements
The optional three phase supply plug for 208v and 240v delta configuration fryers are rated at 60
amps, 250 VAC and is NEMA configuration 15-60P.
Three (3) Phase Requirements
MODEL kW
VOLTAGE
WIRE
SERVICE
MINIMUM WIRE SIZE
AWG (mm)
AMPS
(per leg)
FQEL14 14 208
3
6 (4.11) 39
FQEL14 14 240
3
6 (4.11) 34
FQEL14 14 480
3
8 (2.59) 17
FQEL14 14
220/380
4 6 (4.11) 22
FQEL14 14
230/400
4 6 (4.11) 21
FQEL14 14
240/415
4 6 (4.11) 20
Single (1) Phase Requirements
MODEL kW
VOLTAGE
WIRE
SERVICE
MINIMUM WIRE SIZE
AWG (mm)
AMPS
(per leg)
FQEL14 14 208
2 3 (5.83) 67
FQEL14 14 220
2 3 (5.83) 63
FQEL14 14 240
2 4 (5.19) 58
NOTICE
If this appliance is permanently connected to fixed wiring, it must be connected by
means of copper wires having a temperature rating of not less than 167°F (75°C).
DANGER
This appliance must be connected to a power supply having the same voltage and
phase as specified on the rating plate located on the inside of the appliance door.
DANGER
All wiring connections for this appliance must be made in accordance with the
wiring diagram(s) furnished with the appliance. Refer to the wiring diagram(s)
affixed to the inside of the appliance door when installing or servicing this
equipment.