background image

2

 - fresh air from the central ventilation unit  

- air inlet from the box into the ventilated space

- exhaust air from ventilated space 

- waste air from the box to the central vent. unit

Combined  inlet  and  outlet  ventilation  VBM-V  box  is  designed  to  be  used  in  the  DCV  (demand  controlled  ventilation)  air-
conditioning systems with the possibility of regulation of the inlet and outlet air volume on the basis of actual need of ventilation in
a ventilated space of industrial or residential buildings.

This VBM-V box may be used for flats, hotel apartments, offices, etc. In the box, there are integrated air flow controls, which are
equipped with noise attenuators on the inlet and outlet side. Box is designed to be mounted into the wall or ceiling. On the box
shell, there are integrated rails mounted. The entire box is electrically connected and pre-set in the factory. This ventilation box
may be placed into a furniture case of 600mm size. Each ventilation box may be controlled by a separate remote control. In the
box, there is a power supply and control unit installed for the air flow control with a flexible connection with euro type plug designed
for the sockets of general electric circuits, 1x230V/50Hz.

External remote control for a concealed assembly is led through bushing in the outer box shell into the control unit.

Boxes are designed for the environment protected against climate effects within the air temperatures range from -15°C to +45°C
and within the relative air humidity range max. up to 95% (condensation on the box top or in the internal box components has to
be avoided). Air driven by exhaust has to be free of any abrasive, chemical and sticky additives.

Unless states otherwise, all the sizes are in mm and weights in kg.

Box construction differs according to the order specification.
Ventilation box construction differs according to the side, air inlet part on the neck for SUP fresh ventilation air inlet into the box -
LEFT ("L" code) or RIGHT ("P" code). Another element making difference is the flow rate size of the unit and control unit type.

Summary of Contents for VBM-V Series

Page 1: ......

Page 2: ...ies assembly operation and maintenance Description 2 Construction 2 Size and weight 3 Installation and placement 4 Basic parameters 5 Electric elements connection diagram 5 Pressure losses 8 Noise dat...

Page 3: ...size Each ventilation box may be controlled by a separate remote control In the box there is a power supply and control unit installed for the air flow control with a flexible connection with euro ty...

Page 4: ...3 480 120 240 392 220 100 552 98 44 1250 480 120 240 392 220 100 552 123 44 1250 520 130 260 456 245 107 552 158 32 1400 Removable lid 24 26 31...

Page 5: ...d anchors with load corresponding to the box weight Ceiling installation should be always performed by a removable lid in a downward direction i e to the floor Vertical wall fixing is possible in the...

Page 6: ...RADE 2 GRADE MAX Setting of ventilation intensities for respective grades is within the range of 0 10V MIN 2V 1 GRADE 4V 2 GRADE 6V MAX 10V Remote control is pre set from the factory Different require...

Page 7: ...et for 10min Non presence mode with optional ventilation intensity and time of operation Optional ventilation grades 5 grades Change of setting parameters protected by password Designed for mounting i...

Page 8: ...e and select PRO confirm by select ON or OFF turn time schedule off or on select ON push large digits on the display will show PR01 small digits will show the beginning of the first time interval push...

Page 9: ...60 70 80 90 100 110 120 130 140 150 160 170 180 190 LwA to the pipe for VBM V 125 del p 100Pa del p 250Pa V m3 h L wA dB A 10 15 20 25 30 35 40 30 40 50 60 70 80 90 100 110 120 130 140 LwA to the pipe...

Page 10: ...18 17 14 6 4 D dB 12 11 20 19 20 19 11 6 Shell of the VBM V ventilation box is made of steel zinc plates Box is equipped by flanged with edge rubber sealing Flow rate controllers shells and valve damp...

Page 11: ...er provides a warranty of 24 months for the box from the date of its shipment Such warranty will not apply in case of box use for any other purpose equipment and working conditions as allowed by this...

Page 12: ...ght for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 Fax 420 311 584 810 311 584 382 E Mail man...