8.  The  fire  damper  can  be  integrated  into  a  solid  or  gypsum  wall  construction  or  into  solid  ceiling

construction.  Damper  blade  has  to  be  inside  of  construction  (labelled  with  BUILD  IN  EDGE  on  the
damper body).

9.   All fire dampers has to be closed during installation process. The damper body should not be deformed

in the course of bricking in. Once the damper is built in, its blade should not grind on the damper body
during opening or closing.

10.  To  provide  needed  access  space  to  the  control  device,  all  other  objects  must  be  situated  at  least

350 mm from the control parts of the damper. Inspection hole must be accessible.

7.   Placement of the openings in the wall.

Damper assembly procedures must be done so as all load transfer from the fire separating constructions to
the damper body is absolutely excluded. Back-to-back air - conditioning piping must be hung or supported
so as all load transfer from the back-to-back piping to the damper is absolutely excluded.

2

6

0

4

2

0

(5

0

)

BUIL-IN EDGE

BUILT-IN EDGE

BUI LT- I N   ED G E

Summary of Contents for FDMC

Page 1: ......

Page 2: ...100 40 Fire damper FDMC Solid wall construction Mortar or gypsum Duct 100 40 Installation opening perimeter has to be reinforced by standard drywall profiles Fire damper FDMC Mortar or gypsum Fire pr...

Page 3: ...stallation in a gypsum wall construction 40 100 50 Fire damper FDMC Gypsum plate Fire resistant insulation Mineral stone wool min density 140 kg m Fire protection mastic min thick ness 1 mm Glass fibe...

Page 4: ...l perfectly in all the installation space volume installation gap 5 The distance between the fire damper and the construction wall ceiling must be minimum 75 mm according to EN 1366 2 In case that two...

Page 5: ...er body during opening or closing 10 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control parts of the damper Inspection hole must b...

Page 6: ...ams The blade of fire damper exceeds body of fire damper by the value a There has to be enough space in duct for blade rotation 11 Damper blade overlaps 1 2 S3 S1 S2 S5 S4 S6 5 80 BAT Tf Tf LED 1 2 S3...

Page 7: ...ly e g By releasing the RESET button or restoration of supply from ELECTRICAL FIRE SIGNALISATION 13 Before entering the dampers into operation after assembly and after sequential revisions checks and...

Page 8: ...6724 Hostomice Czech Republic Tel 420 311 706 706 e mail mandik mandik cz www mandik com All rights reserved by Manufacturer Changes to the product can be applied The current product information are a...

Reviews: