background image

KJM MANDÍK Controlling with CPM Wall-Mounted Control 

NONO_CP-M-B_2019-6                                              

www.mandik.cz

          

5  Installation 

The 

CP-M-B

  series  wall-mounted  control  is  designed  for  installation  in  indoor, 

dry  environments.  It  should  be  placed  about  1.5  m  above  the  floor  at  a  place 
with  good  natural  air  circulation.  The  unit  is  suitable  for  mounting  on  most 
commercially available wiring boxes or directly on a wall. 
When  mounting  the  unit,  the  mounting  plate  must  be  fixed  first.  When  the 
electrical contacts are connected, the top panel is hung on the mounting plate 
and clicked in place. 
 
On the underside of the front cover there are two rectangular holes for a small 
flat-blade  screwdriver.  Insert  a  screwdriver  into  each  hole  to  release  the  inner 
latches and to lift the front cover and then to take it off easily. Both the covers 
are plastic.  
 
The unit may only be opened by a qualified electrician.  
Electrical  installation  must  be  performed  in  accordance  with  the  relevant 
regulations and standards.  
Connected cables must meet the insulation requirements of the mains voltage. 
  

Caution! The unit is not protected against accidental connection to ~ 230 
V. 

 

6  Configuration of Climatix Controller 

The Climatix controller must be correctly configured for Mandík air-conditioning 
unit to operate correctly with a wall-mounted control. Configuration is performed 
at the factory based on customer requirements and an electrical diagram that is 
part of the documentation supplied with a specific order. General configuration 
steps are as follows: 
-  Selection,  setting  and  assignment  of  an  input  for  monitoring  the  desired 

temperature. 

-  Selection,  setting  and  assignment  of  an  input  for  monitoring  the  desired 

speed.  

-  Selection and assignment of an output for signalling unit operation. 
-  Selection and assignment of an output for signalling unit fault. 
-  Setting the temperature change range. 
-  Setting the desired speed change range. 
-  Selection of 

Comfort

 or 

Attenuation

 mode when the unit is on. 

-  Selection of 

Off

 or 

Tempering 

mode when the unit is off. 

 

Prior  configuring  the  Climatix  controller,  it  is  necessary  to  familiarize  yourself 
with the manual ‘Measurement and control system for MANDÍK air-conditioning 
units - Detailed instructions and control’. 
 

Installation

 

Opening 

the cover 

Installation 

principles 

Note 

Configuration 

of Climatix 

controller 

Note  

Summary of Contents for CP-M-B

Page 1: ......

Page 2: ...NO_CP M B_2019 6 www mandik cz 2 Table of Contents 1 Introduction 3 2 Technical Data 4 3 Dimensions 4 4 Electrical Wiring 5 5 Installation 6 6 Configuration of Climatix Controller 6 7 Operation of Wal...

Page 3: ...mote control of a Mand k air conditioning unit For use with controllers Climatix POL6xx and POL4xx 1 rotary knob for setting the desired room temperature 1 rotary knob for switching on the air conditi...

Page 4: ...e Unit Power supply voltage 14 24 V DC Maximum consumption 0 4 W Power supply for LEDs 14 24 V DC Input load capacity min 100 k Conductor cross section 0 6 to 0 8 mm2 Recommended cable J Y ST Y 4x2x0...

Page 5: ...supply for run signalling LED 24 V ss 3 FAN Output Fan switching on and required speed 0 10 V 4 TEMP Output Desired temperature correction 0 10 V 5 24V Power supply Power supply 24 V ss 6 GND Power su...

Page 6: ...age Caution The unit is not protected against accidental connection to 230 V 6 Configuration of Climatix Controller The Climatix controller must be correctly configured for Mand k air conditioning uni...

Page 7: ...ning unit starts on and the fans start to run at the minimum speed The minimum speed values are set separately for each fan in the menu on the controller display Components Fans Inlet Attenuation and...

Page 8: ...The unit is in the Start auxiliary mode which is preparing the unit to start the fans ON The unit is started by the fan speed control knob position and the Start auxiliary mode has ended Flashing with...

Page 9: ...is cleaned with a dry painting brush or soft brush or vacuum cleaner when it is off and disassembled The specified maintenance may only be performed by the manufacturer or an authorized service organi...

Page 10: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: