KJM MANDÍK Controlling with CPM Wall-Mounted Control 

NONO_CP-M-B_2019-6                                              

www.mandik.cz

          

.  
 
 
The desired temperature correction value can be changed using the rotary knob 
on  the  control  -  position 

D

.  The  rotary  knob  corrects  the  desired  temperature 

from  the  nominal  temperature.  The  nominal  temperature  is  set  for  each 

Comfort

  or 

Attenuation

  mode  in  menu 

Components 

  Temperature 

Control

.  The  minimum  and  maximum  correction  is  set  in  menu 

Input/Output 

Assignment

  External  Switches

  Desired  Temperature  Min  Max

.  The 

standard setting for 

Min

 and 

Max

 is 5 °C. 

 
The  status of the air-conditioning unit is indicated by the 

Run

 (position  A) and 

Fault

 (position B) LEDs.  

 

Status 

Meaning 

OFF 

The unit is switched off. 

Flashing with 

a period of 1 

sec. 

The unit is in the 

Start

 auxiliary mode, which is preparing the unit to 

start the fans.  

ON 

The  unit  is  started  by  the  fan  speed  control  knob  position  and  the 

Start

 auxiliary mode has ended.  

Flashing with 

a period of 3 

sec. 

The  unit  has  started  automatically  based  on  the  assessed  need  for 
frost protection or room ventilation and the 

Start

 auxiliary mode has 

ended. When the conditions that caused the unit to start up are met, 
the unit switches itself off. This status only occurs if the speed control 
knob is in the 

OFF

 position and the Climatix controller is preset to the 

Tempering

 mode. 

 

 

Status 

Meaning 

OFF 

No fault has occurred. 

Flashing 

Indicates that a new fault has occurred. 

ON 

Indicates a fault that persists after acknowledgment by the 
operator.  

 
The LED functions described above are standard ones and can be customized 
according to client requirements. 
 

Desired 

temperature 

correction 

Unit status 

Run LED 

Fault LED 

Note  

Summary of Contents for CP-M-B

Page 1: ......

Page 2: ...NO_CP M B_2019 6 www mandik cz 2 Table of Contents 1 Introduction 3 2 Technical Data 4 3 Dimensions 4 4 Electrical Wiring 5 5 Installation 6 6 Configuration of Climatix Controller 6 7 Operation of Wal...

Page 3: ...mote control of a Mand k air conditioning unit For use with controllers Climatix POL6xx and POL4xx 1 rotary knob for setting the desired room temperature 1 rotary knob for switching on the air conditi...

Page 4: ...e Unit Power supply voltage 14 24 V DC Maximum consumption 0 4 W Power supply for LEDs 14 24 V DC Input load capacity min 100 k Conductor cross section 0 6 to 0 8 mm2 Recommended cable J Y ST Y 4x2x0...

Page 5: ...supply for run signalling LED 24 V ss 3 FAN Output Fan switching on and required speed 0 10 V 4 TEMP Output Desired temperature correction 0 10 V 5 24V Power supply Power supply 24 V ss 6 GND Power su...

Page 6: ...age Caution The unit is not protected against accidental connection to 230 V 6 Configuration of Climatix Controller The Climatix controller must be correctly configured for Mand k air conditioning uni...

Page 7: ...ning unit starts on and the fans start to run at the minimum speed The minimum speed values are set separately for each fan in the menu on the controller display Components Fans Inlet Attenuation and...

Page 8: ...The unit is in the Start auxiliary mode which is preparing the unit to start the fans ON The unit is started by the fan speed control knob position and the Start auxiliary mode has ended Flashing with...

Page 9: ...is cleaned with a dry painting brush or soft brush or vacuum cleaner when it is off and disassembled The specified maintenance may only be performed by the manufacturer or an authorized service organi...

Page 10: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Reviews: