Temperature controller 70304G | 1.00.02
www.mc-techgroup.com
21
APPENDIX
•
Parametrization for
M&C
-products.
For further product documentation, please see our internet catalogue:
21.1 PARAMETRIZATION FOR STANDARD GAS SAMPLE PROBES
SP2000-H..., SP2200-H..., SP2300-H..., SP2400-H..., SP2500-H..., SP2600-H..., SP2000-H/DIL...
Probe
Version with
PT100
180 °C
PT100
320 °C
Thermo cou-
ple K 180 °C
Thermo cou-
ple K 320 °C
Thermo couple
J 180 °C
Thermo cou-
ple J 320 °C
SP
180
320
180
320
180
320
ALSE
30
30
30
30
30
30
Lo-t
30
30
30
30
30
30
Lfun
2
2
2
2
2
2
Fnct
1
1
1
1
1
1
rASL
3
3
3
3
3
3
SenS
2
2
4
4
4
4
Lin
1
1
12
12
9
9
Parametrization for heated sample tubes :
SP30-H..., SP35-H...
Version with
PT100
200 °C
Thermo couple
K 200 °C
Thermo couple
K 320 °C
Thermo couple
J 200 °C
Thermo cou-
ple J 320 °C
SP
200
200
320
200
320
ALSE
30
30
30
30
30
Lo-t
30
30
30
30
30
Lfun
2
2
2
2
2
Fnct
1
1
1
1
1
rASL
3
3
3
3
3
SenS
2
4
4
4
4
Lin
1
12
12
9
9
Parametrization for dilution probes for the US-market :
SP2000-H/DIL..., SP2006-H/DIL…, SP2006-H280/DIL
Probe version
with
PT100
180 °C
PT100
280 °C
Thermo cou-
ple K 180 °C
Thermo cou-
ple K 280 °C
Thermo couple
J 180 °C
Thermo cou-
ple J 280 °C
SP
180
280
180
280
180
280
ALSE
30
30
30
30
30
30
Lo-t
30
30
30
30
30
30
Lfun
2
2
2
2
2
2
Fnct
1
1
1
1
1
1
rASL
3
3
3
3
3
3
SenS
2
2
4
4
4
4
Lin
1
1
12
12
9
9