A clearance of at least 200 mm must be left in front of the PC to allow open-
ing of the CD-ROM/DVD drive.
Using the bracket supplied, the monitor can be mounted either on a table or
on a wall.
The keyboard is loose and can be placed on a table. The cable length is
1.6 m.
Figure 18: Keyboard for PC
5.5
Cabling
All connecting cables of the individual components required for VTA opera-
tion must be installed in accordance with the rules of electromagnetic com-
patibility. Control cables and power cables must be routed in separate cable
ducts.
The cable length between the servomotor (turbocharger) and the frequency
inverter (VTA control cabinet) is max. 50 m. A max. length of up to 100 m
can be achieved subject to consultation and project clarification with MAN
Diesel & Turbo.
Plant-specific cable lengths are possible by shortening the cables on the
control cabinet side, see operating manual of the turbocharger. The cables
must not be shortened on the servomotor side.
The bending radii must be at least 5 times the cable diameter for fixed instal-
lation and at least 10 times the cable diameter for mobile installation.
Shielded cables must be used for the cabling of all sensors. The shielding
must be connected to a terminal. The area in which the shielding is removed
from the cable must be kept as short as possible.
The control cabinet must be grounded via the ship’s ground or the plant’s
equipotential bonding cable.
The control cabinet is equipped with spring loaded terminals. The entire
cabling to external systems should be executed without wire end ferrules.
Monitor
Keyboard
Electromagnetic
compatibility
Connecting cables
Shielding
Control cabinet grounding
Connection terminals