U-5 IOM
9
CIRCUIT #1
LING ONLY (FIRST STAGE)
TH HOT GAS REHEAT
DEHUMIDIFICATION)
CIRCUIT #2
1ST STAGE HEATING
2ND STAGE COOLING
#1
COMPRESSOR
L3
L3
L1
L1
L2
L2
T3
T3
T3
T2
T2
T2
T1
T1
T1
L3
L3
L3
L2
L2
L2
L1
L1
L1
1M
2M
3M
#2
COMPRESSOR
BLOWER
MOTOR
96
95
SEE NOTE 3
OL
WT
CS
CS
HP
HP
LP
LP
TD
BLA
CK
75 VA
TRANSFORMER
24 VAC
LTC
SEE NOTE 6
(240 SECONDS)
4
2
5
3
1
4R
RPB
ADT
M1
LINE
C
N.C.
3
3
1
1
6R
C1
C2
2
6
5
3R
3
1
1
1
5
5
5
2
2
2
1
RS
S3
3
3
S1
1
2
DM
4
4
1R
2R
SEE NO
TE 4
NOTES:
1. All units are factory-wired to customer order.
For 208 volt units, use the black and red transformer leads.
For 230 volt units, use the black and orange transformer leads.
For 460 volt units, use the black and black/red strip transformer leads.
2. Supply wiring must have copper conductors.
3. An external manual reset overload is used on all 5 HP through 20 HP blower motors. All other blower motors have internal auto reset overloads.
4. The optional “Water Temperature Switch” (WT) is also included in the optional “Low Temperature Package” (TL).
5. Both transformers must be phased identically: L1 is always the transformer’s black lead.
6. If “Low Temperature Cutout Switch” (P/N 71042410) is factory set at 33 F. Its bulb is positioned across the discharge side of the preheat coil.
7. Insulate all unused wire ends.
Ground
Compressor Contactor (Circuit #1)
Compressor Contactor (Circuit #2)
Blower Contactor
Lockout Relay (Circuit #1)
Lockout Relay (Circuit #2)
Lockout Signal Relay
Hot Gas Reheat Relay (Circuit #1)
Cooling Relay (Circuit #2)
Low Temperature Lockout Relay
Dehumidification Lockout in Heating Mode Relay
Hot Gas Reheat Valve (Circuit #1)
4-Way Reversing Valve (Circuit #2)
HP
High Pressure Switch (400 psi)
LP
Low Pressure Switch (7 psi)
CS
Condensate Switch (Optional)
WT
Water Temperature Switch (Optional)
RS
Random Start Relay (25-60 Seconds)
TD
Time Delay Relay (25-60 Seconds)
LTC
Low Temperature Cutout
RPB Reset Push Button
ADT Adjustable Delay-on-Make Timer
DM
Damper Motor
OL
Overload (See Note 3)
1M
2M
3M
1R
2R
3R
4R
5R
6R
7R
HR
RV
Control Voltage Factory Wiring (24 VAC)
Control Voltage Field Wiring (24 VAC)
Line Voltage Factory Wiring
Line Voltage Field Wiring
LEGEND: