background image

Condensing Boiler

10

7/5/99

Two or three second bursts on the pump  at
the initial stage will reduce the risk of foam
formation.

 Sloping the pipe runs towards the vent points
will greatly aid air removal.
Sloping pipes are not just a feature of  gravity
systems  but can greatly aid the pumped
system - because air can move towards a vent
when the pump stops.

Air is dissolved in water but is released when
heated. Always run a system at maximum
temperature for at least 15 minutes to enable
this potential problem to be removed during
commissioning.

COMMISSIONING PROCEDURE

The boiler is fitted with automatic ignition and
will start when the gas cock is open, mains is
connected to the boiler and the controls calling
for heat.

NOTE:

 because of a built in delay, cycles by

the Control Thermostat do not fire the boiler for
3½ minutes, however cycles by the System
Controls are not delayed. Use the System
Isolating switch or a System Thermostat to
avoid the delays during commisioning.

It is strongly suggested that the following
stages of commissioning are followed, and not
an immediate connection of all services. This
procedure prevents substantial amounts of air
being dispersed through  the system as small
bubbles.

Carry out electrical tests as stated in Electrical
Connections if not already done so.

With all radiator valves fully open, fill the
system but do not start pump.

Sealed Systems only :

With the temporary hose connected, fill from
the mains supply , then follow the procedure
below.

Check  for water  soundness  and  rectify
where necessary.

DO NOT TURN ON GAS

Drain the system by opening all draincocks.
This will flush the system of flux and swarf.

Pour 3/4 of the inhibitor in and fill the  system
with  clean water  and  vent air from  radiators
and  pipework.
(Sealed

 Systems only: 

Pour in all the inhibitor,

and fill to required pressure plus 0.3 bar to
allow for venting)

Switch on the electrical supply to the boiler and
switch  the programmer to DHW.

Switch off after about five seconds and vent all
points again.

Repeat this for 5 minutes.
(

Sealed Systems only : 

re-pressurise if

required)

Turn  on pump (do not turn on gas) and run for
at least  30 minutes with 3 port valve in DHW
position most of the time.
Stop pump at five minute intervals and vent
until no more air can be removed  and  air
noises are no longer produced  at  the  boiler.
While the system is venting check again for
water soundness.

Check  for gas soundness (B.S 6891: 1988) in
pipework to boiler using a  manometer.
Open the gas cock and after purging the
system, the boiler will light automatically.
Run  system  at maximum thermostat setting.
Gas  soundness within the boiler should be
checked using sense of smell  and/or  leak
detection fluid. Continue  running  for 15
minutes, venting every 5 minutes.

IMPORTANT Check that the burner pressure
is correct by using a manometer connected
to the multifunctional control, and that the
inlet pressure is at least 20 mbar. If it needs
adjustment this can be made using the nut
under the rubber cap on the underside of
the control (see Fig. 1).

The pilot is non-adjustable.

Check the pilot flame supervision by detecting
the voltage on the Pilot solenoid (P

L

 on the

sequence board), turn off the gas cock. The
voltage on the valve should disappear within
ONE second.

Summary of Contents for 80

Page 1: ......

Page 2: ...SIT 997 113 33 Gas Connection BSP BSP Dry Weight 33 kg 33 kg Water Content 1 4 litres 1 4 litres MAXIMUM Static water head 30 m 30 m MINIMUM Static water head 1 m 1 m MAXIMUM Flow temperature 82 C 82...

Page 3: ...1 Pilot Injector SIT 997 113 33 SIT 997 113 33 Gas Connection BSP BSP Dry Weight 33 kg 37 kg Water Content 1 4 litres 1 6 litres MAXIMUM Static water head 30 m 30 m MINIMUM Static water head 1 m 1 m M...

Page 4: ...systems small bore and microbore domestic central heating systems BS 5546 Installation of gas hot water supplies for domestic purpose 2nd Family Gases BS 5440 1 Flues for gas appliances of rated input...

Page 5: ...r consultation with the Local Gas Region or by a local Gas region contractor An existing meter should be checked preferably by the Gas region to ensure that the meter is adequate to deal with the rate...

Page 6: ...boiler is to be installed in a cupboard or compartment permanent air vents are required for cooling purposes in the cupboard or compartment at both high and low levels The air vents must either commun...

Page 7: ...e and vessel pressure 3 Choose that size or larger from the manufactures range Vessel System Volume litres pressure 50 60 70 100 150 Bar Vessel Volume 0 5 4 4 8 8 12 1 0 8 8 8 12 18 1 5 8 12 12 18 24...

Page 8: ...r rear entry use as supplied For left or right outlet remove appropriate blanking plate and assemble on rear outlet Note Blanking plate holes should be left with a screw to seal them ASSEMBLY OF FLUE...

Page 9: ...ess B S 6891 1988 in pipework to boiler using a manometer Open the gas cock Gas soundness within the boiler should be checked using sense of smell and or leak detection fluid Check the burner bar pres...

Page 10: ...eutral Access to the boiler terminal strip is made by releasing the two plated screws on the front panel and by sliding the bottom section of the boiler forward until it clears The boiler internal wir...

Page 11: ...y where necessary DO NOT TURN ON GAS Drain the system by opening all draincocks This will flush the system of flux and swarf Pour 3 4 of the inhibitor in and fill the system with clean water and vent...

Page 12: ...ermostat to 60oC or lower if preferred Explain and demonstrate the operation of the system to the user Note The boiler is fitted with a blocked drain device and syphon trap to safeguard the boiler and...

Page 13: ......

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...ights the burner and it stays alight until turned off by the control thermostat a safety thermostat in the case of a fault condition or by the system controls The flue thermostat will trip if the flue...

Page 22: ......

Page 23: ...eath the primary Clean as required If in doubt drain the system and remove for inspection 2 Condensate Syphon With a suitable bowl to catch the water unscrew the two drain caps on the underside of the...

Page 24: ...lectrical supply Set burner gas pressure with the adjuster beneath the rubber cap on the underside of the Multifunctional Control The gas valve opens in two steps the first low rate step can be adjust...

Page 25: ...nner cover Remove the Case Pull the electrical connectors off the Control Thermostat Pull off the Control Thermostat Knob Undo the two M4 screws beneath the Knob Remove the retaining clip from the The...

Page 26: ...ve the baffles by releasing the two self tapping screws holding the Front Baffle then undo the four M5 screws holding the baffles onto the Back Panel Remove the Burner as in 13 Undo the four M5 screws...

Page 27: ......

Page 28: ......

Page 29: ......

Page 30: ......

Reviews: