B. Where Not to Install:
Do not install in garages, kitchens, furnace rooms or bathrooms! INSTALL AT LEAST 15
FEET AWAY FROM ANY FUEL BURNING APPLIANCE.
Do not install within 3ft (0.9m) of the following: The door to a kitchen, or a bathroom that
contains a rub or shower, forced air ducts used for heating or cooling, ceiling or whole
house ventilating fans, or other high air flow areas. Avoid excessively dusty, dirty or greasy
areas. Dust, grease or household chemicals contaminate the alarm’s sensors, causing it to
not operate properly.
Place the alarm where drapes or other objects will not block the sensor. CO must be able
to reach the sensors to accurately detect these conditions. Do not install in peaks of
vaulted ceiling, “A” frame ceilings or gabled roofs. Keep out of damp and humid areas.
Install at least one foot away from fluorescent lights, electronic noise may cause nuisance
alarms. Extreme temperatures will affect the sensitivity of the CO Alarm. Do not install in
areas where the temperature is colder than 40 degrees Fahrenheit (4.4 Celsius) or hotter
than 100 degrees Fahrenheit (37.8 Celsius). Place away from doors and windows that
open to the outside.
Step 2
Mounting Instructions:
4. Remove the mounting bracket from the back of the alarm by twisting the alarm.
5. After selecting the proper location for your CO Alarm, drilling two 5.0mm holes in
the ceiling or wall vertically with the distance of 60mm and inserting one plastic
insert into the holes, then attaching the bracket to the plastic insert with the arrow
down to the ground and screwing tightly two screws in the two inserts.
6. Matching the arrow on the back of the alarm with the arrow on the bracket to snap
the alarm on the bracket by twisting the alarm.
Step 3
Testing the Alarm
CAUTION: Due to the loudness of the alarm, always stand an arms length away from
the unit when testing.
The test/reset button has two purposes. It tests the unit’s electronics and reset the unit
during CO alarm. After installation, TEST THE UNITS ELECTRONICS by pressing the test
button for five seconds. A series of beeps will sound. If the unit chirps and red LED flashes
once every 30 seconds with green LED not flashing once every 30 seconds, that means
the unit is malfunctioning. You need to return the unit to our agent for repairing.
If the alarm is sounding, pressing the button will silence the alarm for several minutes.
After the duration, if the CO condition that caused the alert continues, the alarm will
reactivate. The duration spans from 2 minutes to 6 minutes.
The unit needs to be tested
weekly!
If at anytime it does not perform as described, verify power is connected correctly
and that the battery doesn’t need replacing. Clean dust and other buildup off the unit. F it
still doesn’t operate properly call our agent.
Operation Instructions
Test Features
Press the test button for several seconds to test unit’s electronics. The alarm will sound. If
the unit chirp once every 30 seconds with green LED out or “Err” is displaying on the LCD,
that means the unit is malfunctioning. You must return the unit to our agent for repairing.
11/22