8
EN
IMPORTANT: Please read the instruction manual carefully prior to installation and keep
it for future reference.
1. This product should be installed by a registered electrician in accordance with local
standards and electrical regulations.
2. Ensure the mains supply is cut off before installation.
3. Check the unit label for correct supply voltage and frequency.
NOTE
1. The diffuser must not be covered.
2. The rating label must not be removed from the lamp.
3. The fitting must not be link connected (only one connection per fitting).
DESCRIPTION
The fitting is equipped with LED module. Complete with driver. With integrated emer-
gency light inverter which detects when there is a power failure and switches to battery
power. In emergency light mode the light drops to 400lm/5W. The luminaire is provided
with charging indicator/test button. With maintained and non-maintained operation
which can be connected for both options (see wiring diagram).
TECHNICAL SPECIFICATIONS
Art.no:
75 354 74
Wattage:
18W LED
Lumen:
968lm
Dims ØxH:
326x98 mm
Mounting:
Wall or ceiling.
Note:
The terminal block is located under the diffuser. Twist off
the diffuser and connect the luminaire to the mains.
Connection:
To terminal block 3x1.5 mm²
Protection Class:
IP21
LED Power:
Max. 5W
Lumen LED:
400lm
Input Voltage:
230V, 50Hz
Discharge Duration:
2.5h
Battery:
NiMH, 9.6V 2500mA
Ambient temperature: 0ºC – +40ºC