Maktek MR20 Installation, Usage And Maintenance Manual Download Page 16

 BEFORE FIRST OPERATION.

 First Operation must be done only by MAKTEK Autorised Services for safe and efficient running and validation of the warranty.

before firs use;

Gas type and pressure must be checked.

Be sure that gas line is open and reaches the radiant.

Be sure that electric line is open and and current reaches to the radiant.

Be sure gas and electric lines are isolated from each other.

FIRST OPERATION:

IMPORTANT:  This guide definetly must be read before first operation and kept.

Open the fuse key which heater is connected after being sure of installation done in the correct way in accordance with warnings and informations 
stated in this guide and after reading this guide.

If there is energy entrance for the system yellow led on bottom of burner  flashes constant. Please observe this.If yellow led doesn't flash use 
error detection guide and search for probable reasons of the problem and call maktek autorised service if necessary.
NOTE:  A little bit bending is normal  can ve  acceptable because of the hot working temperature of radiant.

ERRORS  AND SOLUTION METHODS:

  is important for not If there is a problem at radiant heater's running or radiant doesn't work please try to find the source of the problem by using the 
error detection guide on page 11. It is important that you do not have to wait for the service for a problem that you may be able to solve by yourself ,
or that you are not trying to correct a malfunction that requires service intervention.

IMPORTANT: Flashing red led means reset is needed. How to make reset:  Shut down the fuse key. And wait 15 
seconds an open again.

RUNNING AND ERROR CONDITIONS:
Yellow led on the burner flashes while radiant is powered. After running with safety control, 10 seconds pre- sweeping operation is performed.  After
pre-sweeping, ignition starts. Ignition operation stats with the arc that powereing ignition electrode. At that time gas valve powered also. If inginition 
occured successfully, ionisation electrode detects the   flame ans stops the ignition. 
 If flame doesn't occure for any reason, radiant shows error and red led flashes.  Close the fuse key radiant connected, wait 15 seconds and lift 
the key again after being sure that gas source is open.  If  error condition occures after resetting, reasons must be searched. In electrical 
problems, electric connections inside the radiant, problems can be caused from the building electricity line ( weak grounding, ground ressistance, 
phase neutral polarisation etc.) must be considered.

                                                                                                     14

Summary of Contents for MR20

Page 1: ...RADIANT HEATER INSTALLATION USAGE AND MAINTENANCE MANUAL MR20 MR30 MR 40 MR55...

Page 2: ...stallation 9 Heater gas and electricity line connection schema 10 Burner electricity schema 11 USER INSTRUCTIONS Safety Warnings 12 13 First use of radiant 14 Error detection and generating solutions...

Page 3: ...tural Gas G20 Ignition System Automatic ionisation controlled Nominal power kW 20 30 40 55 Nominal power kcal h 17200 25800 34400 47300 Gas input pressure mbar 20 20 20 20 Injector diameter mm 4 4 5 5...

Page 4: ...iate mounting installation setting service and maintenance may cause the product to malfunction resulting in the aplliance to go out of warranty or even may cause injuries to people Please read throug...

Page 5: ...arda yan c ve parlay c maddeler bulundurulmamal d r Please check the voltage frequency and electricity feeding before the firs operating Check the fuel type which would be used and input pressure Area...

Page 6: ...with TS EN 416 1 standarts It is necessary to pay attention for installation distance that was stated in this guide for maksimu efficiency thermal comfort and reducing fire risk Number Equivalent of...

Page 7: ...brackets must be hanged on strong place which can lift the weight of radiant heater All chains must be in equal length on a same line and brackets must be on scale Distance between chains and brackets...

Page 8: ...mney will fix and hanger profile 4 Tighten the krom pipe end point s U bolt in the way completely tighten the pipe which burner inserted tighten other U bolts in the way pipe will be released by help...

Page 9: ...end without interspacing Center the half of the pipe press clamp on one pipe and the other half on other pipe and press the clamp by using M8 imbus screw nut and washer as shown on picture Place the h...

Page 10: ...nd pipe s burner fix end There are 5 each screw holes on 3mm diameter one end and 4mm diameter other end of the reflectors For making radiant connections healthly superimpose 4mm diameter perforated e...

Page 11: ...ion Of Burner Mate the cast barrel at the end of burner into the crome pipe and push till the fulcrum lean on pipe Finally fix burner to the chrome pipe by using M8 Setscrew You can tighten setscrews...

Page 12: ...e used Maximum chimeny length is 6 meters 3 MAKING CHIMNEY CONNECTION When chimney connection is making chimney must be connected with a down slope to prevent first burning perspiration and rain water...

Page 13: ...11...

Page 14: ...nd pipe connection points of the gas line Do not move the heater while running or it is hot even it is off Do not try to fix or touch it Close the fuse key to stop running of radiator Do not interfere...

Page 15: ...held responsible for financial and emotional damage caused from this NOTE Unconfirmed part mounting to the system or making changes without permission can cause damages on radiant and cause the damag...

Page 16: ...running or radiant doesn t work please try to find the source of the problem by using the error detection guide on page 11 It is important that you do not have to wait for the service for a problem t...

Page 17: ...nect try to run the radiant in this way Sorun z l rse kablo u lar bu pozisyonda ba l kals n If the problem continues the reason is not phase neutral polarisation and reconnect the phase neutral cable...

Page 18: ...it is balanced in hanged place 3 Checking the leakages in gas circuit if necessary providing sealing by changing joints and o rings 4 Checking the general conditions of components that continues burn...

Page 19: ...nd errors can be caused from inappropriate storage conditions in inappropriate places 5 Damages and errors can be caused while carrying the the radiant from one place to another 6 Damages and errors c...

Page 20: ...REPLACEMENT AND VE REPAIR METHOD DISMANTLING THE BURNER For changing any part in burner box Remove the gas and electric connections Remove the setscrews which are in point of burner and radiant pipes...

Page 21: ...unter clockwise to reach the electrodes and injector easily turning clockwise tightens turning counter clockwise loosen pic 2b Use 11nr key for dismantling and mounting operations for cleaning or chan...

Page 22: ...k kart t br l r kutusundan kart t n z Bak n z Resim 3b Remove the card from burner by removing the electrode cables that are mounted at left side of the card cable socket connected to card and the sre...

Page 23: ...21...

Page 24: ...Combining Gas Valve and Bridge Parts 22...

Page 25: ...23...

Page 26: ...Pcs 1 Pcs 1 Pcs Fuse box 1 Pcs 1 Pcs 1 Pcs 1 Pcs 220V elektric cable 1 Pcs 1 Pcs 1 Pcs 1 Pcs M8 Setscrew 2 Pcs 2 Pcs 2 Pcs 2 Pcs 3 9 x 6mm Sheet metal screw 10 Pcs 15 Pcs 35 Pcs 35 Pcs M4 x 30mm screw...

Page 27: ......

Reviews: