Appendixes
II - Shutter and Blinds
Since all the channels are identical, also their COs have identical characteristics, differing only in their
number. The GO number increment is θ = 30.
Table 17: Shutter and Blinds Channel [x]-[x+1]'s specific COs' description (x=1...n-1, where n
is the number of channels available)
Function
#GO
GO Name
IN/OUT
DPT
Up / Down Control
0+x*
θ
Move Up / Down
IN
1.008
Wind Alarm
1+x*
θ
Wind Alarm
IN
1.002
Scene Control
3+x*θ
Scene Control
IN
18.001
Slat angle Up/Down and Stop Up/Down
4+x*θ
Slat Angle | Stop Up / Down
IN
1.008
Shutter Position
5+x*θ
Shutter Position (%)
IN
5.001
Blinds Position
6+x*θ
Blinds Angle (°)
IN
5.003
6+x*θ
Blinds Position (%)
IN
5.001
Jamming
7+x*θ
Jamming
IN
1.002
Rain Alarm
8+x*θ
Rain Alarm
IN
1.002
Shutter Position Indication
10+x*θ Shutter Position Indication
OUT
5.001
Blinds Position Indication
11+x*θ Blinds Angle Indication
OUT
5.003
11+x*θ Blinds Position Indication
OUT
5.001
Up Movement Status Indication
14+x*θ Up Status Indication
OUT
1.001
Down Movement Status Indication
29+x*θ Down Status Indication
OUT
1.001
User’s Manual