Majestic • PEARL36STIN, PEARL36PRIN Owner’s Manual • 2478-981 Rev. C • 6/18
22
Intellifire™ Touch - (continued)
Symptom
Possible Cause
Corrective Action
Pilot sparks for 60 sec, but will not
light, 3 Red/1 Green Lockout.
No gas supply.
Verify incoming gas line ball valve is ‘Open’. Verify inlet pres-
sure is within requirement for gas type used. Contact gas sup-
plier.
ECM has poor ground.
Verify wiring, check valve harness black wire is securely
grounded to metal chassis.
Gas valve defective.
Check pilot valve solenoid kick and hold voltages during igni
-
tion cycle. Kick V should be >1 V, hold V minimum 0.26 V. If
voltages are OK, replace gas valve.
Pliot lights but main burner does
not light. Pilot continues to spark
for 60 sec then goes into 3 Red/1
Green Lockout.
No flame detected. Flame
rectification issue.
Check if white sense lead is securely connected to ‘S’ terminal
of
IFT-
ECM. Check resistance of sense lead between sense
rod tip and connector to
IFT-
ECM, should be less than 1 ohm
- if not, replace pilot assembly. Check system ground, ensure
black valve harness wire is securely attached to metal chassis.
Check wiring for damage. With system OFF, check resistance
between tip of sense rod and pilot hood, should be resistance
(>1 M-ohm).
No flame detected or sense
rod contamination.
With glass assembly installed, verify pilot flame is engulfing
flame sense rod on pilot assembly. Verify inlet gas pressure
is correct for gas type. Polish flame sense rod with fine steel
wool to remove any contaminants that may have accumulated.
Pilot lights and rectifies, but main
burner does not light.
Main valve solenoid.
Check if green wire in valve harness is connected to green
main valve solenoid. Check main valve solenoid resistance,
nominal is 60 ohms. If open or shorted, replace valve. Verify
valve inlet pressure is correct for gas type.
Pilot and main do not light, ECM
goes into 5 Red/1 Green Lockout.
Power Vent (PV) Failure.
Power Vent blower defective - check wiring to
IFT-
ACM, check
if blower is working. Check if PV pressure switch is connected
to brown and black wire in 6-pin valve wire harness. Check if
pressure switch is closed (shorted) when PV blower is running.
Refer to PV troubleshooting instructions.
Appliance lights and runs for a few
minutes then shuts down and/or
appliance cycle ON and OFF with
less than 60 sec of ON time.
Shorted or loose connection in
flame detection circuit.
Check if white sense lead is securely connected to ‘S’ terminal
of
IFT-
ECM. Check resistance of sense lead between sense
rod tip and connector to
IFT-
ECM, should be less than 1 ohm
- if not, replace pilot assembly. Check system ground, ensure
black valve harness wire is securely attached to metal chassis.
Check wiring for damage. With system OFF, check resistance
between tip of sense rod and pilot hood, should be resistance
(>1 M-ohm).
Poor flame rectification or
contaminated sense rod.
With glass assembly installed, verify pilot flame is engulfing
flame sense rod on pilot assembly. Verify inlet gas pressure
is correct for gas type. Polish flame sense rod with fine steel
wool to remove any contaminants that may have accumulated.
Verify no soot deposits are in sense rod to pilot hood gap.
Logs are set up wrong.
Remove and re-install logs per the log placement instructions.
Damaged pilot assembly.
Verify the pilot assembly ceramic insulator around the flame
sensing rod is not cracked, damaged or loose. Check re
-
sistance between tip of sense rod and
IFT-
ECM connector,
should be less than 1 ohm. Replace pilot assembly if damage
is detected.