11
NVB Series B-Vent Gas Fireplace
7412950
FP567
Fig. 13
Venting configurations.
�����
����������������������
��������
Venting Runs
��
��
��
��
��
��
��
��
��
��
��
��
��
��
��
������������
��������������������������������
Horizontal Run (in feet)
Vertical Run (in feet)
A
A:
Vertical installations up to 40 feet (12m) in
height. Up to a 6 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 90-degree elbows or four
45-degree elbows.
B:
Vertical installations up to 40 feet (12m) in
height. Up to a 10 ft. horizontal vent run can be
installed within the vent system using a
maximum of two 45-degree elbows.
B
= Acceptable venting configuration
= Unacceptable venting configuration
FP567a
Fig. 14
Venting configurations when installing 36GSKBB.
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
2
4 6
8 10 12 14 16 18 20
A
FP567a
Venting Run
Graph
8/17/99 djt
Horizontal Run (in feet)
Vertical Run (in feet)
= Acceptable venting configuration
= Unacceptable venting configuration
A: Vertical installation up to 40 feet (12m) in
height. Up to a 16 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 90 degree elbows
or four 45 degree elbows.
B: Vertical installation up to 40 feet (12m) in
height. Up to a 20 ft. horizontal vent run
can be installed within the vent system
using a maximum of two 45 degree elbows.
B