17
Majestic • MDVI30IN, MDVI35IN, MDVI30IL, MDVI35IL Installation Manual • 2205-980 Rev. H • 12/16
Figure 7.6
Masonry
Factory Built
Wood Burning
Remove 18 inch x 18 inch
fl
ashing on cap by removing 3
screws. Connect both the LINK-ZC-ADPB to Class A Pipe
and the termination cap to the LINK-ZC-ADPB with the
self tapping screws provided.
OPTIONAL LINK-ZC-ADPB
FOR USE WITH CLASS A
WOODBURNING PIPE
EXHAUST
AIR
VENT PIPE
TERMINATION
CAP
LINK-DV30B
LINKSQ-DV30
Installation*
LINK-DV4-30B
LINKSQ-DV4-30
Installation**
INLET AIR
VENT PIPE
WARNING:
DO NOT BLOCK
THIS PIPE END!
INLET AIR
VENT PIPE
EXHAUST
AIR
VENT PIPE
Note: Untwist the
pipe while extend-
ing it, to achieve full
30’ length.
OR
Note
: The LINK-DV4-30B and LINKSQ-DV4-30 systems
REQUIRE this insulation.
To prevent odors and cold air drafts, it may be necessary to
place non-combustible insulation or
fi
eld fabricated metal
plates around the vent pipe
fl
ues as they go through the
damper.
*LINK-DV30B/LINKSQ-DV30: This installation may perform better
and allow less cold air in
fi
ltration in negative pressure settings.
**LINK-DV430B/LINKSQ-DV4-30:
• This installation may be more susceptible to cold air in
fi
ltration and
the effects of negative pressure on the appliance’s performance.
• Depending on the chimney cleanliness, consider using the
full length intake so as to lessen the possibility of sense rod
contamination and
fl
ame recti
fi
cation issues.