background image

21

75D2525

DVM Series Direct Vent Gas Fireplace

VentIng InstallatIon 

note: #1222da reducer must be used when 4x6

B\,

venting is preferred. #7tdVp58 reducer must be used 

when  4"x7"  venting  is  preferred.  reducer  must  be 

installed directly onto unit at fireplace collar before 

vertical rise. 

Below grade InstallatIons

When it is not possible to meet the required vent terminal 

clearances of 12" above grade level, a snorkel kit is recom-

mended. It allows installation depth down to 7" (178 mm) 

below grade level. The 7" (178 mm) is measured from the 

center of the horizontal vent pipe as it penetrates through 

the wall.

ensure that sidewall venting clearances are observed. 

If venting system is installed below ground, we recom-

mend a window well with adequate and proper drainage 

to be installed around the termination area.

If installing a snorkel, a minimum 24" vertical rise is nec-

essary. The maximum horizontal run with the 24” vertical 

pipe is 36". This measurement is taken from the collar of 

the fireplace (or transition elbow) to the face of the exterior 

wall.  Refer  to  the  Sidewall  Venting  Graph  for  extended 

horizontal run if the vertical exceeds 24".
1.  Establish vent hole through the wall. Page 16, 

Figure 

17.

2.  Remove soil to a depth of approximately 16" below base 

of snorkel. Install drain pipe. Install window well (not 

supplied). Refill hole with 12" of coarse gravel leaving 

a clearance of approximately 4" below snorkel.

 Figure 

27.

3.  Install vent system.
4.  Ensure a watertight seal is made around the vent pipe 

coming through the wall.

Figure 26 - 

Exterior Wall Framing Dimensions 

for 4 x 6

B\,

" or 4" x 7" Venting  

VO584-100
Vent Opening
2/99   djt

9

Z\x

"

(241 mm)

9

Z\x

"

(241 mm)

combustible wall

framing

VO584-100

7

Z\x

(190 mm)

FP1965
below grade install

24”

Minimum

Figure 27 -  

Below Grade Installation

Screws

Minimum 

4" Clearance

Ground

Window 

Well 

Gravel 

Drain 

Foundation Wall 

Firestop 

FP1965

5.  Apply  high  temperature  sealant  caulking  (supplied) 

around the 5" and 8" snorkel collars.

6.  Slide the snorkel into the vent pipes and secure to the 

wall.

7.  Level  the  soil  so  as  to 

maintain  a  4"  clearance 

below snorkel. 

Figure 27

If  the  foundation 

is  recessed,  use 

recess  brackets 

(not  supplied)  for 

securing  lower 

portion  of  the 

snorkel.  Fasten 

brackets  to  wall 

first,  then  secure 

to  snorkel  with 

self drilling #8 

x  1/2  sheet 

metal  screws. 

It  will  be  nec-

essary to extend vent pipes out as far as the protruding 

wall face. 

Figure 28

FP1966
snorkel

Figure 28 - 

Snorkel Installation, Recessed Foundation

Foundation

Recess 

Watertight Seal 

Around Pipe 

Sheet Metal 

Screws 

Snorkel

Wall Screws

FP1966

w

arn

Ing

  do not back fill around snorkel.

  a  clearance  of  at  least  4"  must  be 

maintained between the snorkel and 

the soil.

Summary of Contents for 500DVM

Page 1: ...n in manufactured home USA only or mobile home and must be installed in accordance with the manufacturer s instructions and the manufactured home construction and safety standard Title 24 CFR Part 328...

Page 2: ...lation 25 Fireplace Installation 28 Check Gas Type 28 Gas Pipe Installation 29 Check Gas Pressure Millivolt 30 Electrical Installation Millivolt 30 Electrical Wiring 30 Remote Wall Mounted Switch 31 O...

Page 3: ...it is not properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning ar...

Page 4: ...ese appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER TEST...

Page 5: ...RS Switch Ignitor 1 2 Nailing Flange 5 8 Nailing Flange 1 2 Nailing Flange Eyebrow Insulation Board Standoff FP2407 WARNING Do not remove insulation board GAS pressures HIGH ELEVATIONS Input ratings...

Page 6: ...1067 mm F 32ZB zn 837 mm 38ZB zn 989 mm G 42M zn 1079 mm 42M zn 1079 mm H 34Z x 876 mm 34Z x 876 mm I 23C zn 589 mm 23C zn 589 mm J 34B 880 mm 34B 880 mm K 16Z 410 mm 19Z 486 mm L 14 zn 370 mm 14 zn 3...

Page 7: ...e Sealant Approved for use with Propane LPG Resistant to sulfur compounds WARNING Do not fill spaces around firebox with insulation or other materials This could cause a fire NOTE COLD CLIMATE INSULAT...

Page 8: ...o heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting section fou...

Page 9: ...m 6 152 mm Min FP2408 DVM MDV clearances 12 305 mm Maximum Depth Ceiling Side Wall Combustible Mantel FP2408 Figure 4 Ceiling and Side Wall Clearances 12 10 8 6 4 256O 12 10 6M 956O 856M 7 6 FP2409 Ma...

Page 10: ...all and the fireplace surround are sealed a 300 F minimum sealant material General Electric RTV103 or equivalent must be used The fireplace must be secured to the floor and or to framing studs as show...

Page 11: ...d gasket Figure 7 After conversion to top vent configuration the 5 127 mm flue pipe should be concentric with the 8 203 mm outer collar within 1 4 WARNING FP1991 remove screws Flue Pipe Cover Flue Pip...

Page 12: ...ps Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthorized modifica...

Page 13: ...along horizontal length until flue pipe penetrates outside wall A minimum 1 clearance to combustibles permitted all around flue at outside wall WARNING Horizontal sections of this vent system require...

Page 14: ...walls of your home This is especially important in cold climates Insulation should be considered a combustible material Maintain proper clearances to all combustible materials NOTICE Treatment of fir...

Page 15: ...bove the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for appliances 1...

Page 16: ...Figure 13 Rear Wall Venting Graph Horizontal Dimension From the Outside Face of the Wall to the Back of the Fireplace Vertical Dimension From the Floor of Unit to the Center of the Horizontal Vent Pi...

Page 17: ...ing and termination instructions for further instructions 3 Locate and cut the vent opening in the wall For com bustible walls first frame in opening Combustible Interior Walls Cut a 12Z x H x 10Z x W...

Page 18: ...able Refer to Page 15 Minimum clearance between vent pipes and combusti ble materials is 3 on top and 1 from bottom and sides unless otherwise noted Exception Outside wall with firestop 1 all around p...

Page 19: ...calculations and unless specifically mentioned should be ignored when calculating venting layouts FP1176 max 90 bends Figure 20 Maximum Three 3 90 Elbows Per Installation 3 x 90 Elbows 3 x 90 Elbows F...

Page 20: ...center of the hole should align with the center line of the horizontal rigid vent pipe end Allow 1 4 minimum rise per foot Figure 25 WARNING You may use a reducer from 5 x8 to 4 x6B or 4 x7 for horizo...

Page 21: ...mately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snorkel Figure 27 3 Install vent s...

Page 22: ...e vent system using a maximum of two 90 elbows Figure 30 Up to two 45 elbows may be used within the horizontal run For each 45 elbow used on the horizontal plane the maximum horizontal length must be...

Page 23: ...1 Maximum Elbow Usage FP1969 offset w wallstrap Figure 32 Offset with Wall Strap and 45 Elbows Roof Flashing Wall Strap 45 Elbows Ceiling Firstop FP1669 Flat ceiling installation 1 Cut a 10Z x 267 mm...

Page 24: ...ng roof lines steep pitched roofs and other similar factors may cause poor draft or down drafting in high winds Increasing the vent height may solve this problem NOTE If the vent pipe passes through a...

Page 25: ...uter adapter rings are required to start all flex runs Never install damaged or torn flexible venting Over tightening clamps may rip tear or otherwise damage flexible venting The adapter kit does not...

Page 26: ...e means to support the flexible vent 5 Flexible vent spacers are to be installed at inter vals prescribed by the flexible vent manufacturer and in such a way as to maintain concentric inner and outer...

Page 27: ...ove gear clamp 4 x 7 Rigid Pipe Length Flex to Pipe Adapter DVFFA 8 Gear Clamp 1C v Flexible Pipe and Adapter Outer Collar Overlap UL1777 Flex Vent Figure 43 Typical Pipe Connection Gear Clamp FP1976...

Page 28: ...s not provided A CSA design certified equipment shutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Purchase the CSA design certified equipment shutoff valve from your...

Page 29: ...em valves We recommend that you install a sediment trap drip leg in supply line as shown in Figure 46 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system betwe...

Page 30: ...firmly to reseal Do not over torque Check test points for gas leaks NOTE Captured screws for pressure reading are located in the same place in both valve types Millivolt and Electronic Electrical Wir...

Page 31: ...tend beyond the wall switch wire length provided NOTE Extended lengths of wire may cause the fireplace not to function properly Longer length of wire is permitted if the wire is made out of larger gau...

Page 32: ...or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to inspect the appliance and to...

Page 33: ...gnitethepilot Keep knob fully depressed for a few seconds Release and check that pilot continues to burn If the pilot does not stay lit repeat steps 1 and 2 Pilot Position Check for gas leaks in each...

Page 34: ...the burner to ignite Pilot position Depress and turn knob to pilot position to keep burner off while maintain ing the pilot light Depress and turn knob clockwise to OFF position to turn off gas milli...

Page 35: ...Electrical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 A...

Page 36: ...Do not extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from jun...

Page 37: ...LP Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in...

Page 38: ...d Blower or the control will not work correctly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the f...

Page 39: ...ol FP2685 BLOTSDV blower wiring OPTIONAL FAN BLOWER SYSTEMS BLOTSDV AUTOMATIC THERMOSTAT BLOWER Figure 53 BLOTSDV Blower Wiring Diagram FP2685 Before installing the blower wire the receptacle into an...

Page 40: ...r s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will n...

Page 41: ...mell gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 5 Press ON button Sparker will spark and pilot flame w...

Page 42: ...ild Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode Thermostat Auto Flame Blower Modulation...

Page 43: ...nattended You may disable this feature if you wish NOTE By disabling this feature your fireplace may continue to operate unattended 2 When the master switch is in the ON position pressing the ON butto...

Page 44: ...hen Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off The nex...

Page 45: ...ssembly FP2417 Figure 56 Install Canopy FP2418 install canopy Eyebrow Screws FP2418 FP2419 install glass frame Figure 57 Remove Glass Frame Glass Frame Clamps FP2419 CAUTION Each clamp has a quick spr...

Page 46: ...he rear of the burner on the bracket Fig ure 59 LG665 Rear Log LG667 DVM left middle log Figure 59 Place Rear Log Left Middle Log LG667 3 Place the left middle log by aligning the holes in the bottom...

Page 47: ...the front right log by setting the notch on the bottom of the log on the very far right tong of the grate and resting the log on the leg of the grate Figure 62 LG670 DVM upper logs Upper Left Log Upp...

Page 48: ...l with a brush or vacuum WARNING Turn off gas before servicing fireplace It is recommended that a qualified service technician perform these check ups at the beginning of each heating season LG671 DVM...

Page 49: ...ials may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Canopy Installation and Glass Removal...

Page 50: ...the thermocouple connec tion at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter le...

Page 51: ...ust the pilot flame for maximum flame impingement on thermocouple A Check for flue product leak Replace defective pipe section B Check horizontal venting piping is running upward 1 4 per foot Do not r...

Page 52: ...und Check gas supply Go through Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery vol...

Page 53: ...56D2135K 56D2263K 4 Glass Frame Assy 1 56D2143K 56D2269K 5 Eyebrow 1 56D4041 56D4038 6 Insulation Board 1 56D2197 56D2216K Accessories Field Installed Options 7 Firebrick Tavern Brown 1 FBMDV500TB FB...

Page 54: ...54 75D2525 DVM Series Direct Vent Gas Fireplace REPLACEMENT PARTS 1 2C 2I 2T 2 4 5 6 3 8 9 7 10 11 12 13 14 15 16 752525 DVM millivolt parts Standing Pilot Millivolt Control...

Page 55: ...030 69D0030 69D0030 69D0030 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 7 Injector 1 57D1030 20H3144 56D0614 57D0680 8 Burner Assy 1 75D2509 75D...

Page 56: ...56 75D2525 DVM Series Direct Vent Gas Fireplace REPLACEMENT PARTS SIGNATURE COMMAND SYSTEM 1 2 3 4 19 5 6 7 8 9 13 14 15 16 17 752523 MDV DVM SC parts 12...

Page 57: ...0 80D0010 80D0010 80D0010 11 Wire Command Ctr Control Box 2 not shown 1 80D0008 80D0008 80D0008 80D0008 12 A C Adapter 6 Volt 1 80D0041 80D0041 80D0041 80D0041 Accessories 13 Hand Held Remote Control...

Page 58: ...DVM 1 Rear Log 1 1 75D2016 75D2016 2 Left Middle Log 2 1 75D2017 75D2017 3 Right Middle Log 3 1 75D2018 75D2018 4 Left Front Log 4 1 75D2019 75D2019 5 Right Front Log 5 1 75D2020 75D2020 6 Upper Left...

Page 59: ...uvers 8 L36PWM L48PWM 3 Screen Frame Black 1 500DVMSD 600DVMSD 4 Cabinet Door Frame Black 1 VSDVC500CDFB VSDVC600CDFB 4 Cabinet Door Frame Iron Age 1 VSDVC500CDFIA VSDVC600CDFIA 4 Cabinet Door w Scree...

Page 60: ...24 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 4D36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4D48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe Extension galvanized 46...

Page 61: ...Length 58DVA 09 1207 5DT 09 3 4 12 Pipe Length 58DVA 12 1206 5DT 12 5D12 3 4 24 Pipe Length 58DVA 24 1204 5DT 24 5D24 3 4 36 Pipe Length 58DVA 36 1203 5DT 36 5D36 3 4 48 Pipe Length 58DVA 48 1202 5DT...

Page 62: ...stable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7T...

Page 63: ...Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 5 x 8 to 4 x 7 Adapter 7TDVP58 Flex Adapter Starter Kit DVFFA 8 Twist Lock Elbows 45 Elbow for Vertica...

Page 64: ...64 75D2525 DVM Series Direct Vent Gas Fireplace...

Page 65: ...65 75D2525 DVM Series Direct Vent Gas Fireplace...

Page 66: ...o comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Pl...

Page 67: ...e void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect m...

Page 68: ...09 Recherchez dans la brochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency 500DVMNV 71 7 50...

Reviews: