DVM Series Direct Vent Gas Fireplace
clearances
clearances to comBustIBles
follow these instructions carefully to ensure safe installation. failure to
follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
w
arn
Ing
72”
(1829 mm)
Minimum
12”
(305 mm)
Minimum
6”
(152 mm)
Min.
FP2408
DVM MDV clearances
12”
(305 mm)
Maximum Depth
Ceiling
Side Wall
Combustible
Mantel
FP2408
Figure 4 -
Ceiling and Side Wall Clearances
12”
10”
8”
6”
4”
2
56O
”
12"
10
6M
”
9
56O
”
8
56M
”
7”
6”
FP2409
Mantel clearance
Top of Fireplace
Opening
Stud
Header
Standoff
Insulation
Board
FP2409
side View
45°
1”
2
56O
”
3”
5”
6”
56O
”
56O
”
56O
”
FP2410
mantel leg clearance
Finish Wall
Combustible
Material Area
FP2410
Figure 5 -
Mantel Clearances
mantel clearances
note:
The combustible area above the facing must not protrude
more than 1/2" from the facing. If it does, it is considered a mantel
and must meet the mantel requirements listed in this manual.
w
arn
Ing
never obstruct or modify the air inlet or
outlet grilles (louvers). this may create a
fire hazard.