34
360 DVS Series Direct Vent Fireplaces
10006326
D
E
F
FC108
SIT
regulator
conversion
10/03
OFF
PILOT
ON
FC108
Fig. 49
Replace regulator.
10. Reassemble fireplace in the reverse order, except
for the window frame assembly. Leave this off until
after unit has been checked for leaks and the gas
supply has been bled.
11. After bleeding the gas line and checking for leaks
with a soap solution, replace the window frame as-
sembly.
12. Fire up the unit. Check for flame impingement on
the logs, adjusting them as necessary.
13. Check manifold and supply pressures against the
appliance specifications.
The procedure for converting from one gas
to another is the same regardless of the
initial gas used. The only variations are in
orifice sizes and component part numbers.
Your authorized service provider will en-
sure correct parts are used.
LOH
I
HV120
Honeywell valve
conversion
9/24/02 djt
Regulator Cap
Conversion
Screw
Pressure Regu-
lator Housing
HV120
Fig. 50
Honeywell conversion screw replacement.
Honeywell Gas Control Valve
(Fig. 50)
The Honeywell valve fitted to this unit is suitable for use
with LP or Natural Gas. It is converted to the required
gas application by installing a color-coded conversion
screw.
a) Using a suitable small screwdriver, lift out the cen-
tral regulator cap from the “HI/LO” knob on the valve.
b) Unscrew the exposed conversion screw.
c) Insert the new color coded conversion screw. Do
not overtighten the screw; it must be finger- tight.
d) Refit the regulator cap.
e) Mount conversion label supplied with the conver-
sion screw to the valve in a visible position.